Speed Varies During Operation; Operation Mode Is Not Changed Properly - Mitsubishi Electric FR-F720-0.75K to 110K Instruction Manual

Table of Contents

Advertisement

Check first when you have a trouble
5.5.8

Speed varies during operation

Check
points
Load
Load varies during an operation.
Frequency setting signal is varying.
The frequency setting signal is affected by EMI.
Input
signal
Malfunction is occurring due to the undesirable current
generated when the transistor output unit is connected.
Multi-speed command signal is chattering.
Fluctuation of power supply voltage is too large.
Pr. 80 Motor capacity setting is improper for the
capacities of the inverter and the motor for Simple
magnetic flux vector control.
Wiring length is too long for V/F control, and a voltage
Parameter
drop occurs.
Setting
Hunting occurs by the generated vibration, for example,
when structural rigidity at load side is insufficient.
5.5.9

Operation mode is not changed properly

Check
points
Input
Start signal (STF or STR) is ON.
signal
Pr. 79 setting is improper.
Parameter
Setting
Operation mode and a writing device do not
correspond.
276
Possible Cause
Possible Cause
Countermeasures
Select Simple magnetic flux vector control
Check the frequency setting signal.
Set filter to the analog input terminal using Pr. 74 Input
filter time constant.
Take countermeasures against EMI, such as using
shielded wires for input signal lines.
Use terminal PC (terminal SD when source logic) as a
common terminal to prevent a malfunction caused by
undesirable current.
Take countermeasures to suppress chattering.
Change the Pr. 19 Base frequency voltage setting (about
3%) under V/F control.
Check the Pr. 80 Motor capacity setting.
Adjust Pr. 0 Torque boost by increasing with 0.5%
increments for low-speed operation.
Change to Simple magnetic flux vector control.
Disable automatic control functions, such as energy
saving operation, fast-response current limit function,
regeneration avoidance function, Simple magnetic flux
vector control and stall prevention.
Adjust so that the control gain decreases and the level of
safety increases.
Change Pr. 72 PWM frequency selection setting.
Countermeasures
Check that the STF and STR signals are OFF.
When either is ON, the operation mode cannot be
changed.
When Pr. 79 Operation mode selection setting is "0" (initial
value), the inverter is placed in the External operation
mode at input power ON. To switch to the PU operation
mode, press
on the operation panel (press
when the parameter unit (FR-PU04/FR-PU07) is used) .
At other settings (1 to 4, 6, 7), the operation mode is
limited accordingly.
Check Pr. 79, Pr. 338, Pr. 339, Pr. 550, Pr. 551, and select
an operation mode suitable for the purpose.
Refer
to
page
75
166
46
30
84
75
74
75
158
Refer
to
page
177
177
, 177,
186