Function assignment of external
terminal and control
Setting
Signal
Positive
Negative
Name
Logic
Logic
13
113
Y13
14
114
FDN
15
115
FUP
16
116
RL
17
MC1
18
MC2
19
MC3
25
125
FAN
26
126
FIN
45
145
RUN3
46
146
Y46
47
147
PID
48
148
Y48
64
164
Y64
70
170
SLEEP
79
179
Y79
85
185
Y85
90
190
Y90
91
191
Y91
92
192
Y92
93
193
Y93
94
194
ALM2
95
195
Y95
96
196
REM
98
198
LF
122
Function
Output when the output power is lower than
Zero current
the Pr. 152 setting for longer than the time
detection
set in Pr. 153.
Output when the feedback value falls below
PID lower limit
the lower limit of PID control.
Output when the feedback value rises above
PID upper limit
the upper limit of PID control
PID forward/reverse
Output when forward rotation is performed in
rotation output
PID control.
Electric bypass MC1
Used when the bypass-inverter switchover
Electric bypass MC2
function is used.
Electric bypass MC3
Fan fault output
Output at the time of a fan alarm.
Output when the heatsink temperature
Heatsink overheat
reaches about 85% of the heatsink overheat
pre-alarm
protection operation temperature.
During inverter
Output when the inverter is running and start
running and start
command is on.
command is on
During deceleration at
Output when the power failure-time
occurrence of power
deceleration function is executed.
failure
(retained until release)
During PID control
Output during PID control.
activated
Output when the absolute value of deviation
PID deviation limit
exceeds the limit value.
During retry
Output during retry processing.
PID output
Output when the PID output interruption
interruption
function is executed.
Output in pulses every time the accumulated
Pulse train output of
output power of the inverter reaches the
output power
Pr.799 setting.
Output during power failure or under voltage
DC feeding
of AC power.
Output when any of the control circuit
capacitor, main circuit capacitor and inrush
Life alarm
current limit circuit or the cooling fan
approaches the end of its service life.
Output when a fault occurs due to the
Fault output 3
internal circuit failure of inverter wiring
(power-off signal)
mistake.
Turned on and off alternately every time the
Power saving
power saving average value is updated
average value
when the power saving monitor is used.
updated timing
Cannot be set to Pr. 195 and Pr. 196 (relay
output terminal).
Average current value and maintenance
Current average
timer value are output as pulses.
value monitor signal
Cannot be set to Pr. 195 and Pr. 196 (relay
output terminal).
Output when the fault occurs. Continues
outputting the signal during inverter reset
Fault output 2
and stops outputting after reset is cancelled.
*2
Maintenance timer
Output when Pr. 503 rises to or above the Pr.
signal
504 setting.
Output to the terminal when a value is set to
Remote output
the parameter.
Output when an alarm (fan failure or
Alarm output
communication error warning) occurs.
Operation
Related
Refer
Parameters
to Page
Pr. 152, Pr. 153
126
Pr. 127 to Pr. 134,
221
Pr. 575 to Pr. 577
Pr. 135 to Pr. 139,
233
Pr. 159
Pr. 244
240
266
123
Pr. 261 to Pr. 266
145
Pr. 127 to Pr. 134,
221
Pr. 575 to Pr. 577
Pr. 127 to Pr. 134,
Pr. 241, Pr. 553, Pr.
221
554, Pr. 575 to Pr.
577, C42 to C45
Pr. 65 to Pr. 69
148
Pr. 127 to Pr. 134,
221
Pr. 575 to Pr. 577
Pr. 799
129
Pr. 30, Pr. 70
107
Pr. 255 to Pr. 259
241
124
Pr. 52, Pr. 54,
Pr. 158, Pr. 891 to
153
Pr. 899
Pr. 555 to Pr. 557
245
124
Pr. 503, Pr. 504
244
Pr. 495 to Pr. 497
128
196,
Pr. 121, Pr. 244
240