(2) Multi-speed setting higher than speed 4 (Pr. 24 to Pr. 27, Pr. 232 to Pr. 239)
⋅ Frequency from speed 4 to speed 15 can be set according to the combination of the RH, RM, RL and REX signals. Set
the running frequencies in Pr. 24 to Pr. 27, Pr. 232 to Pr. 239. (In the initial value setting, speed 4 to speed 15 are invalid.)
⋅ For the terminal used for REX signal input, set "8" in any of Pr. 178 to Pr. 186 to assign the function.
Speed 5
Speed 6
Speed 8
Speed 4
Speed 7
ON ON ON
RH
ON
ON
ON
RM
ON
ON
RL
REX
*
When "9999" is set in Pr.232 Multi-speed setting (speed 8), operation is performed at frequency set in Pr.6 when RH, RM and RL are turned off and
REX is turned on.
REMARKS
⋅ The priorities of the frequency commands by the external signals are "jog operation > multi-speed operation > terminal 4 analog
input > terminal 2 analog input". (Refer to page 160 for the frequency command by analog input)
⋅ Valid in External operation mode or PU/external combined operation mode (Pr. 79 = "3" or "4").
⋅ Multi-speed parameters can also be set in the PU or External operation mode.
⋅ Pr. 24 to Pr. 27 and Pr. 232 to Pr. 239 settings have no priority between them.
⋅ When a value other than "0" is set in Pr. 59 Remote function selection, the RH, RM and RL signals are used as the remote setting
signals and the multi-speed setting becomes invalid.
⋅ When making analog input compensation, set "1" in Pr. 28 Multi-speed input compensation selection.
CAUTION
⋅ The RH, RM, RL, REX signals can be assigned to the input terminal using any of Pr. 178 to Pr. 189 (input terminal function
selection). Changing the terminal assignment using Pr. 178 to Pr. 189 (input terminal function selection) may affect the other
functions. Make setting after confirming the function of each terminal.
♦ Parameters referred to ♦
Pr. 1 Maximum frequency, Pr. 2 Minimum frequency
Pr. 15 Jog frequency
Refer to page 90
Pr. 28 Multi-speed input compensation selection
Pr. 59 Remote function selection
Pr. 178 to Pr. 189 (input terminal function selection)
Speed 10
Speed 11
Speed 12
Speed 9
Speed 13
Speed 14
Speed 15
ON ON ON ON
ON ON
ON ON
ON
ON
ON
ON
ON
ON
ON ON ON ON ON ON
*
Refer to page 82
Refer to page 92
Refer to page 93
Refer to page 115
Frequency setting by external terminals
Forward
rotation
Time
Multi-Speed Operation
Connection Example
Inverter
STF
REX
10
RH
2
RM
5
RL
SD
89
4