Mitsubishi Electric FR-F720-0.75K to 110K Instruction Manual page 30

Table of Contents

Advertisement

400V class (when input power supply is 440V)
Terminal
Applicable
Screw
Inverter Type
Size
*4
FR-F740-0.75K to
M4
3.7K
FR-F740-5.5K
M4
FR-F740-7.5K
M4
FR-F740-11K
M4
FR-F740-15K
M5
FR-F740-18.5K
M5
FR-F740-22K
M6
FR-F740-30K
M6
FR-F740-37K
M6
FR-F740-45K
M8
FR-F740-55K
M8
FR-F740-75K
M8
FR-F740-90K
M10
FR-F740-110K
M10
FR-F740-132K
M10
FR-F740-160K
M10
FR-F740-185K
M12 (M10)
FR-F740-220K
M12 (M10)
FR-F740-250K
M12 (M10)
FR-F740-280K
M12 (M10)
FR-F740-315K
M12 (M10)
FR-F740-355K
M12 (M10)
FR-F740-400K
M12 (M10)
FR-F740-450K
M12 (M10)
FR-F740-500K
M12 (M10)
FR-F740-560K
M12 (M10)
*1
For the FR-F740-55K or less, the recommended cable size is that of the cable (e.g. HIV cable (600V class 2 vinyl-insulated cable)) with continuous
maximum permissible temperature of 75°C. Assumes that the surrounding air temperature is 50°C or less and the wiring distance is 20m or less.
For the FR-F740-75K or more, the recommended cable size is that of the cable (e.g. LMFC (heat resistant flexible cross-linked polyethylene insulated
cable)) with continuous maximum permissible temperature of 90°C. Assumes that the surrounding air temperature is 50°C or less and wiring is performed
in an enclosure.
*2
For the FR-F740-45K or less, the recommended cable size is that of the cable (THHW cable) with continuous maximum permissible temperature of 75°C.
Assumes that the surrounding air temperature is 40°C or less and the wiring distance is 20m or less.
For the FR-F740-55K or more, the recommended cable size is that of the cable (THHN cable) with continuous maximum permissible temperature of 90°C.
Assumes that the surrounding air temperature is 40°C or less and wiring is performed in an enclosure.
(Selection example for use mainly in the United States.)
*3
For the FR-F740-45K or less, the recommended cable size is that of the cable (PVC cable) with continuous maximum permissible temperature of 70°C.
Assumes that the surrounding air temperature is 40°C or less and the wiring distance is 20m or less.
For the FR-F740-55K or more, the recommended cable size is that of the cable (XLPE cable) with continuous maximum permissible temperature of 90°C.
Assumes that the surrounding air temperature is 40°C or less and wiring is performed in an enclosure.
(Selection example for use mainly in the Europe.)
*4
The terminal screw size indicates the terminal size for R/L1, S/L2, T/L3, U, V, W, and a screw for earthing (grounding).
A screw for earthing (grounding) of the 185K or more is indicated in ( ).
The line voltage drop can be calculated by the following formula:
3 × wire resistance[mΩ/m] × wiring distance[m] × current[A]
line voltage drop [V]=
Use a larger diameter cable when the wiring distance is long or when it is desired to decrease the voltage drop (torque
reduction) in the low speed range.
CAUTION
· Tighten the terminal screw to the specified torque.
A screw that has been tighten too loosely can cause a short circuit or malfunction.
A screw that has been tighten too tightly can cause a short circuit or malfunction due to the unit breakage.
· Use crimping terminals with insulation sleeve to wire the power supply and motor.
Crimping
(Compression)
Tightening
Terminal
Torque
N·m
R/L1, S/L2,
R/L1, S/L2,
U, V, W
T/L3
1.5
2-4
2-4
1.5
2-4
2-4
1.5
5.5-4
5.5-4
1.5
5.5-4
5.5-4
2.5
8-5
8-5
2.5
14-5
8-5
4.4
14-6
14-6
4.4
22-6
22-6
4.4
22-6
22-6
7.8
38-8
38-8
7.8
60-8
60-8
7.8
60-8
60-8
14.7
60-10
60-10
14.7
80-10
80-10
14.7
100-10 100-10
14.7
150-10 150-10
24.5
150-12 150-12
24.5
100-12 100-12
2×100
24.5
100-12 100-12
2×100
24.5
150-12 150-12
2×125
24.5
150-12 150-12
2×150
24.5
200-12 200-12
2×200
24.5
C2-200 C2-200 2×200
24.5
C2-250 C2-250 2×250
24.5
C2-250 C2-250 2×250
24.5
C2-200 C2-200 3×200
1000
Main circuit terminal specifications
Cable Sizes
2
AWG/MCM
HIV, etc. (mm
)
*1
Earth
R/L1, S/L2,
U, V, W
(Ground)
T/L3
T/L3
cable
2
2
2
14
2
2
3.5
12
3.5
3.5
3.5
12
5.5
5.5
8
10
8
8
8
8
14
8
14
6
14
14
14
6
22
22
14
4
22
22
14
4
38
38
22
1
60
60
22
1/0
60
60
38
1/0
60
60
38
3/0
80
80
38
3/0
100
100
38
4/0
125
125
38
250
150
150
38
300
2×100
38
2×4/0
2×100
38
2×4/0
2×125
38
2×250
2×150
38
2×300
2×200
60
2×350
2×200
60
2×400
2×250
60
2×500
2×250
100
2×500
3×200
100
3×350
2
PVC, etc. (mm
)
*2
Earth
R/L1, S/L2,
U, V, W
U, V, W
(Ground)
T/L3
cable
14
2.5
2.5
14
2.5
2.5
12
4
4
10
6
6
8
10
10
8
16
10
6
16
16
4
25
25
4
25
25
2
50
50
1/0
50
50
1/0
50
50
3/0
50
50
3/0
70
70
4/0
95
95
250
120
120
300
150
150
2×4/0
2×95
2×95
2×4/0
2×95
2×95
2×250
2×120
2×120
120
2×300
2×150
2×150
150
2×350
2×185
2×185
2×95
2×400
2×185
2×185
2×95
2×500
2×240
2×240
2×120
2×500
2×240
2×240
2×120
3×350
3×185
3×185
2×150
*3
2.5
4
4
10
10
16
16
16
16
25
25
25
25
35
50
70
95
95
95
2
21