• FR-F720-15K, FR-F740-15K or more
1) Remove the upper screws.
2) Remove the lower screws.
3) Pull the jumper toward you to
remove.
4) Connect the separate power supply
cable for the control circuit to the
upper terminals (R1/L11, S1/L21).
CAUTION
· Be sure to use the inverter with the jumpers across terminals R/L1-R1/L11 and S/L2-S1/L21 removed when supplying power
from other sources. The inverter may be damaged if you do not remove the jumper.
· The voltage should be the same as that of the main control circuit when the control circuit power is supplied from other than the
primary side of the MC.
· The power capacity necessary when separate power is supplied from R1/L11 and S1/L21 differs according to the inverter
capacity.
15K or less
200V class
60VA
400V class
60VA
· If the main circuit power is switched off (for 0.1s or more) then on again, the inverter resets and a fault output will not be held.
R1/
S1/
L11
L21 Power supply
terminal block
for the control circuit
R/L1S/L2 T/L3
MC
Main power supply
FR-F720-15K
FR-F740-15K, 18.5K
Power supply
terminal block for
the control circuit
18.5K
22K or more
80VA
80VA
60VA
80VA
Main circuit terminal specifications
3)
Power supply terminal block
for the control circuit
1)
2)
4)
FR-F720-37K or more
FR-F720-18.5K to 30K
FR-F740-37K or more
FR-F740-22K, 30K
R1/L11
S1/L21
U
V
W
2
25