Special operation and frequency control
<Set point input calibration>
1) Setting with terminal 2 input
1. Apply the input voltage of 0% set point setting (e.g. 0V) across terminals 2-5.
2. Enter in C2 (Pr. 902) the frequency which should be output by the inverter at the deviation of 0% (e.g. 0Hz).
3. In C3 (Pr. 902), set the voltage value at 0%.
4. Apply the voltage of 100% set point (e.g. 5V) to across terminals 2-5.
5. Enter in Pr. 125 the frequency which should be output by the inverter at the deviation of 100% (e.g. 60Hz).
6. In C4 (Pr. 903), set the voltage value at 100%.
2) Setting with Pr. 133
When both or one of C42 (Pr.934) and C44 (Pr.935) is "9999".
For the set point, set a % converted value in the range of 0 to 100%.
When both of C42 (Pr.934) and C44 (Pr.935) ≠ "9999".
For the set point, set PID coefficient, which corresponds with 0 to 100%.
<Measured value calibration>
1) When both or one of C42 (Pr.934) and C44 (Pr.935) is "9999".
1. Apply the input current of 0% measured value (e.g. 4mA) across terminals 4-5.
2. Make calibration using C6 (Pr. 904).
3. Apply the input current of 100% measured value (e.g. 20mA) across terminals 4-5.
4. Make calibration using C7 (Pr. 905).
2) When both of C42 (Pr.934) and C44 (Pr.935) ≠ "9999".
1. Apply the input current of 0% measured value (e.g. 4mA) across terminals 4 and 5.
2. Set PID display value at 0% measured value (example: 15(°C)) to C42 (Pr.934) , and calibrate C43 (Pr.934).
3. Apply the input current of 100% measured value (e.g. 20mA) across terminals 4 and 5.
4. Set PID display value at 100% measured value (example: 35(°C)) to C44 (Pr.935), and calibrate C45 (Pr.935).
REMARKS
⋅ The frequency set in C5 (Pr. 904) and Pr. 126 should be the same as set in C2 (Pr. 902) and Pr. 125.
The results of the above calibration are as shown below:
Pr.934,
Pr.133
Pr.935
Setting
Setting
9999
Both or one
is 9999
Other than
9999
Other than
9999
230
Set Point Setting
(Terminal 2)
Set point
(%)
100
0
0
5 (V)
Set point signal input
(Pr.133)
Set point
(%)
100
0
C5(Pr.904)
Pr.126
Set point setting
(Pr.133)
Set point
(%)
100
0
C42(Pr.934)
C44(Pr.935)
Set PID coefficient
corresponding with 0 to 100%.
Measured Value
(Terminal 4)
Measured
Value
(%)
100
0
0
4
20
(mA)
C6(Pr.904)
C7(Pr.905)
Measured value
input signal
Measured
value
(%)
100
0
0
4
20
(mA)
C43(Pr.934)
C45(Pr.935)
Measured value
input signal
Manipulated Variable
Manipulated
Variable(Hz)
60
(Pr.125)
0
C2(Pr.902)
0
100
Deviation(%)