SMC Networks HRS012-A*-10-* Operation Manual page 99

Thermo chiller
Hide thumbs Also See for HRS012-A*-10-*:
Table of Contents

Advertisement

42.
Select temperature alarm monitoring method from the table below with [▲] key or [▼]
key, and confirm by pressing "SEL".
Set value
Item
Continuous
monitoring
Automatic
monitoring
Monitoring
timer
Automatic
monitoring
Monitoring
timer
∗ Settings of this function and example of alarm generating timing for 5.15.3 "Setting of temperature alarm
monitoring method and generation timing".
Monitoring start timer Setting and Checking
43.
Press the [SEL] key once.
Setting screen of the monitoring start timer is displayed on the digital display.
PV
SV
44.
Select monitoring start timer from the table below with [▲] key or [▼] key, and confirm
by pressing "SEL".
Set value
to
∗ Settings of this function and example of alarm generating timing for 5.15.3 "Setting of
temperature alarm monitoring method and generation timing".
HRS Series
Table 5.15-22
Alarm monitoring starts at the same time as
operation starts.
When the circulating fluid temperature is
outside of the alarm threshold range at the
time of operation start, the alarm will not be
generated until the temperature comes
inside the alarm threshold range.
Alarm will not be generated until it reaches
the time set for the AS.22 "Monitoring start
start
timer" after the operation starts.
Alarm monitoring starts when it reaches the
set time.
Alarm will not be generated until it reaches
the time set for the AS.22 "Monitoring start
timer" after the operation starts.
Alarm monitoring starts when it reaches the
+
set time.
start
When the circulating fluid temperature
enters the alarm threshold range before it
reaches the set time, the alarm monitoring
will be started at that time.
Table 5.15-23
Explanation
Setting and checking are impossible when "0:
Continuous monitoring" or "1: Automatic
monitoring" is selected for the setting of AS21
"Temperature alarm monitoring method".
Sets the time when alarm monitoring starts
Setting unit is 1 minute.
Chapter 5
Display and setting of various functions
List of set value
Explanation
List of set value
HRX-OM-M090
Initial value
(Default setting)
Initial value
(Default setting)
5.15 Alarm customize function
5-47