HRX-OM-M090
Chapter 5
Display and setting of various functions
14.
Select slave addresses (simple communication protocol) from the table below with [▲]
key or [▼] key, and confirm by pressing "SEL".
Set value
to
Communication speed (simple communication protocol) Setting/checking
15.
Press the [SEL] key once.
The set screen of communication speed (simple communication protocol) is displayed
on the digital display.
PV
SV
16.
Select communication speed (simple communication protocol) from the table below with
[▲] key or [▼] key, and confirm by pressing "SEL".
Set value
BCC (simple communication protocol) Setting/checking
17.
Press the [SEL] key once.
The set screen of BCC (simple communication protocol) is displayed on the digital
display.
PV
SV
5.18 Communication function
5-58
Table 5.18-8 List of set value
Explanation
Setting/checking are not available unless the
serial protocol setting is simple
communication protocol.
Sets of slave addresses for simple
communication protocol.
Set range is 1 to 99.
Table 5.18-9 List of set value
Explanation
Setting/checking are not available unless the
serial protocol setting is simple
communication protocol.
1200bps
2400bps
4800bps
9600bps
19200bps
Initial value
(Default setting)
Initial value
(Default setting)