Slave addresses(MODBUS) Setting and checking
9.
Press the [SEL] key once.
The set screen of slave addresses (MODBUS) is displayed on the digital display.
PV
SV
10.
Select slave addresses (MODBUS) from the table below with [▲] key or [▼] key, and
confirm by pressing "SEL".
Set value
to
Communication speed (MODBUS) Setting and checking
11.
Press the [SEL] key once.
The set screen of communication speed (MODBUS) is displayed on the digital display.
PV
SV
12.
Select communication speed (MODBUS) from the table below with [▲] key or [▼] key,
and confirm by pressing "SEL".
Set value
Slave addresses(simple communication protocol) Setting and checking
13.
Press the [SEL] key once.
The set screen of slave addresses (simple communication protocol) is displayed on the
digital display.
PV
SV
HRS Series
Table 5.18-6 List of set value
Explanation
Setting/checking are not available unless the
serial protocol setting is MODBUS.
Sets of slave addresses for MODBUS.
Set range is 1 to 99.
Table 5.18-7 List of set value
Explanation
Setting/checking are not available unless the
serial protocol setting is MODBUS.
9600bps
19200bps
Chapter 5
Display and setting of various functions
HRX-OM-M090
Initial value
(Default setting)
Initial value
(Default setting)
5.18 Communication function
5-57