SMC Networks HRS012-A*-10-* Operation Manual page 89

Thermo chiller
Hide thumbs Also See for HRS012-A*-10-*:
Table of Contents

Advertisement

Display
Changing
resistivity drop
Lower
limit
resistivity drop
Temperature alarm
Monitoring method
Monitoring start timer
Range over
Detection timer
*1:This function is available for customers who have purchased the drain pan set (part no.: HRS-WL001).
*2 : This function is available for customers who have purchased the electric resistivity sensor set (part no.:
HRS-Dl001).
1.
Press and hold the [MENU] key for approx. 2 sec.
Repeat pressing the key until the setting screen for alarm buzzer sound [
appears on the digital display.
PV
SV
Low tank level Setting and checking
2.
Press the [SEL] key once.
The set screen of changing of low tank level is displayed on the digital display.
PV
SV
3.
Select changing of low tank level from the table below with [▲] key or [▼] key, and
confirm by pressing "SEL".
Set value
HRS Series
Table 5.15-2 List of set alarm customize function(2/2)
Item
of
electric
Set the operation when the alarm No. AL35
"Electric resistivity drop" is generated.
Sets the detection level for the alarm of alarm
of
electric
NO. AL35 "Electric resistivity drop".
Alarm signal is generated when the level
becomes lower than this level.
One alarm monitoring method can be selected
from four methods for AL04 "Detection temp for
the circulating fluid discharge temp. increase"
and AL06 "Detection temp. for circulating fluid
discharge temp. drop".
Alarm will not be generated during the set period
of time after starting operation. Alarm monitoring
starts when it reaches the set time.
After starting the alarm monitoring, the alarm will
not be generated right away and will be kept not
generated for the set period of time for AL04
"Detection temp for the circulating fluid discharge
temp. increase" and AL06 "Detection temp. for
circulating fluid discharge temp. drop", when the
temperatures goes out of the set range.
[MENU]
Press and
hold
PV
SV
Table 5.15-3 List of set value
Explanation
Operation continues when this alarm signal is
generated.
Operation is stopped when this alarm signal is
generated.
Chapter 5
Display and setting of various functions
Contents
[MENU]
Press and
hold
PV
SV
HRX-OM-M090
Initial value
(Default setting)
OFF
0.2MΩ・cm
0
----
5
]
[MENU]
Press and
hold
PV
SV
Initial value
(Default setting)
5.15 Alarm customize function
5-37

Advertisement

Table of Contents
loading

Table of Contents