SMC Networks HRS012-A*-10-* Operation Manual page 64

Thermo chiller
Hide thumbs Also See for HRS012-A*-10-*:
Table of Contents

Advertisement

HRX-OM-M090
Chapter 5
Display and setting of various functions
Check of the accumulated operation time of the fan motor
9.
Press the [SEL] key once.
The accumulated operation time of the fun motor is displayed on the digital display.
PV
SV
Displays the accumulated operation time of the fan motor. Refer to Table 5.4-2 for the
display.
AL29 Fan motor maintenance alarm is generated when the accumulated operation
time of the fan motor reaches 20,000 hours (
Chapter 6 Alarm indication and trouble shooting.
Water-cooled refrigerated type does not have the fan motor. The accumulated time of
the digital display shows "
Also, AL29 fan motor maintenance alarm is not generated.
Check of the accumulated operation time of the compressor
10.
Press the [SEL] key once.
The accumulated operation time of the compressor is displayed on the digital display.
PV
SV
Displays the accumulated operation time of the compressor. Refer to Table 5.4-2 for
the display.
AL30 Compressor maintenance alarm is generated when the accumulated operation
time of the compressor reaches 50,000 hours (
Chapter 6 Alarm indication and trouble shooting.
Check of the accumulated operation time
11.
Press the [SEL] key once.
The accumulated operation time is displayed on the digital display.
PV
SV
Displays the accumulated operation time. Refer to Table 5.4-2 for the display.
5.4 Inspection monitor menu
5-12
) or more. For details, refer to
".
) or more. For details, refer to
HRS Series

Advertisement

Table of Contents
loading

Table of Contents