Ieee 1613 Type Tests; Table 26: Ieee 1613 Type Tests - RuggedCom RuggedRouter RX1000 Family Installation Manual

Industrially hardened cyber security appliance
Hide thumbs Also See for RuggedRouter RX1000 Family:
Table of Contents

Advertisement

Technical Specifications

5.6 IEEE 1613 Type Tests

IEEE
IEEE
Test
1613
Clause
C37.90.3
9
C37.90.2
8
C37.90.1
7
C37.90.1
7
C37.90
6
C37.90
6

Table 26: IEEE 1613 Type Tests

NOTES:
If the unit contains copper ports the IEEE 1613 conformance is Class 1
(During disturbance errors may occur but recovery is automatic).
If the unit contains all fiber ports the IEEE 1613 conformance is Class 2
(During disturbance no errors will occur).
®
RuggedCom
- Rev.122
Description
Enclosure Contact
ESD
Enclosure Air
Radiated RFI
Enclosure ports
Signal ports
D.C. Power ports
Fast Transient
A.C. Power ports
Earth ground ports
Signal ports
D.C. Power ports
Oscillatory
A.C. Power ports
Signal ports
H.V. Impulse
D.C. Power ports
A.C. Power ports
Signal ports
Dielectric
D.C. Power ports
Strength
A.C. Power ports
46
Test Levels
+/- 8kV
+/- 15kV
35 V/m
+/- 4kV @ 2.5kHz
+/- 4kV
+/- 4kV
+/- 4kV
2.5kV common mode @ 1MHz
2.5kV common & differential mode @
1MHz
2.5kV common & differential mode @
1MHz
5 kV (Failsafe Relay)
5 kV
5 kV
2kV AC(Failsafe Relay)
1.5kV DC
2kV AC
®
RuggedRouter
RX1000 Family

Advertisement