Figure 34: Irig-B Simplified Schematic; Table 14: Irig-B Output Specifications - RuggedCom RuggedRouter RX1000 Family Installation Manual

Industrially hardened cyber security appliance
Hide thumbs Also See for RuggedRouter RX1000 Family:
Table of Contents

Advertisement

Communication Ports
4.10.3 IRIG-B Outputs
The PTP Card supports both IRIG-B outputs in both Amplitude Modulated (AM) and
Pulse Width Modulation (PWM) formats. Specifically, for the AM output IRIG-B122 &
IRIG-B123 are supported and for the PWM IRIG-B002 & IRIG-B003 are supported.
Enabling of the AM and PWM outputs is done through software.
The number of IRIG-B devices that can be connected to the AM or PWM source is
dependent on the cabling type and length as well as the input impedances of the
devices. Figure 34 shows a simplified circuit diagram of the interface between the
IRIG-B source and connected devices.
S o u rce
V s

Figure 34: IRIG-B Simplified Schematic

The maximum number of devices (N) that can be connected to the source is
determined by checking if the source current (I
devices is less than the maximum drive current the source can provide, and verifying
that the load voltage (V
required voltage.
Parameter
Output Current (I
Output Voltage (V
Output Impedance (R

Table 14: IRIG-B Output Specifications

4.10.4 Pulse per Second Output (PPS)
The PTP Card supports one Pulse-Per-Second output. When enabled through
software, it outputs a 5V pulse every second.
®
RuggedCom
- Rev.122
C a b lin g
R s
R c
) the connected devices see is greater than the minimum
L
)
40 mA total between two output ports
S
)
S
)
S
38
D e vice
R
/N
L
) required to drive the connected
S
Typical Value
5 V
p-p
25 Ω
®
RuggedRouter
RX1000 Family

Advertisement

Table of Contents
loading

Table of Contents