5. EMI And Environmental Type Tests
Test
IEEE C37.90.3
IEEE C37.90.2
IEEE C37.90.1
IEEE C37.90.1
IEEE C37.90
IEEE C37.90
a
Meets Class 2 requirements for an all fiber configuration. Class 1 for copper ports.
Table 5.2. IEEE 1613 (C37.90.x) EMI Immunity Type Tests
Test
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-30
IEC 60255-21-1
IEC 60255-21-2
Table 5.3. Environmental Type Tests
RuggedCom® RuggedBackbone™
Description
ESD
Radiated RFI
Fast Transient
Oscillatory
H.V. Impulse
Dielectric Strength
Description
Cold Temperature
Dry Heat
Humidity (Damp Heat, Cyclic)
Vibration
Shock
Enclosure Contact
Enclosure Air
Enclosure ports
Signal ports
D.C. Power ports
A.C. Power ports
Earth ground ports
Signal ports
D.C. Power ports
A.C. Power ports
Signal ports
D.C. Power ports
A.C. Power ports
Signal ports
D.C. Power ports
A.C. Power ports
a
Test Ad
Test Bd
Test Db
95% (non-condensing), 55°C , 6 cycles
31
RX5000 Installation Guide Rev 107
Test Levels
+/-2kV, +/-4kV, +/- 8kV
+/-4kV, +/-8kV, +/-15kV
35 V/m
+/- 4kV @ 2.5kHz
+/- 4kV
+/- 4kV
+/- 4kV
2.5kV common mode @1MHz
2.5kV common, 1kV diff. mode@1MHz
2.5kV common, 1kV diff. mode@1MHz
5kV (Fail-Safe Relay output)
5kV
5kV
2kVAC
2kVDC
2kVAC
Test Levels
-40°C, 16 Hours
+85°C, 16 Hours
2g @ (10 - 150) Hz
30g @ 11mS