Installation
Dual Power Supplies – DC and AC Inputs
3.2.3

Figure 13: DC and AC Power Supply Wiring Example

NOTES:
88-300VDC rated equipment: A 300VDC appropriately rated circuit breaker
must be installed.
100-240VAC rated equipment: A 250VAC appropriately rated circuit breaker
must be installed.
A circuit breaker is not required for 48 or 24VDC rated power supplies.
Separate circuit breakers must be installed and separately identified.
Equipment must be installed according to the applicable country wiring
codes.
®