Emi And Environmental Type Tests - RuggedCom RuggedVDSL RS930 Instructions Manual

6-port managed ethernet switch with dual port ethernet over vdsl uplinks
Table of Contents

Advertisement

TEST
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
Burst (Fast Transient)
IEC 61000-4-5
IEC 61000-4-6
Induced (Conducted) RFI
IEC 61000-4-8
IEC 61000-4-29
Voltage Dips & Interrupts
IEC 61000-4-11
IEC 61000-4-12
IEC 61000-4-16
Mains Frequency Voltage
IEC 61000-4-17
Ripple on D.C. Power Supply
IEC 60255-5
IEC 60255-5
Test
IEEE C37.90.3
IEEE C37.90.2
IEEE C37.90.1
IEEE C37.90.1
IEEE C37.90
IEEE C37.90
Test
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-30
Humidity (Damp Heat, Cyclic)
IEC 60255-21-1
IEC 60255-21-2
Notes: 1. Class 2 refers to "Measuring relays and protection equipment for which a very high security margin is required or where the vibration levels are very high, ( e.g. shipboard application and for severe transportation conditions")
www.RuggedCom.com
6-Port Managed Ethernet Switch with Dual Port Ethernet over VDSL Uplinks

EMI and Environmental Type Tests

IEC 61850-3 EMI TYPE TESTS
Description
Enclosure Contact
ESD
Enclosure Air
Radiated RFI
Enclosure ports
Signal ports
D.C. Power ports
A.C. Power ports
Earth ground ports 3
Signal ports
Surge
D.C. Power ports
A.C. Power ports
Signal ports
D.C Power ports
A.C. Power ports
Earth ground ports 3
Magnetic Field
Enclosure ports
D.C. Power ports
A.C. Power ports
Signal ports
Damped Oscillatory
D.C. Power ports
A.C. Power ports
Signal ports
D.C. Power ports
D.C. Power ports
Signal ports
Dielectric Strength
D.C. Power ports
A.C. Power ports
Signal ports
H.V. Impulse
D.C. Power ports
A.C. Power ports
IEEE 1613 (C37.90.x) EMI IMMUNITY TYPE TESTS
Description
Enclosure Contact
ESD
Enclosure Air
Radiated RFI
Enclosure ports
Signal ports
D.C. Power ports
Fast Transient
A.C. Power ports
Earth ground ports3
Signal ports
Oscillatory
D.C. Power ports
A.C. Power ports
Signal ports
H.V. Impulse
D.C. Power ports
A.C. Power ports
Signal ports
Dielectric Strength
D.C. Power ports
A.C. Power ports
Environmental Type Tests
Description
Cold Temperature
Dry Heat
Vibration
Shock
RuggedVDSL™ RS930L
Test Levels
+/- 8kV
+/- 15kV
20 V/m
+/- 4kV @ 2.5kHz
+/- 4kV
+/- 4kV
+/- 4kV
+/- 4kV line-to-earth, +/- 2kV line-to-line
+/- 2kV line-to-earth, +/- 1kV line-to-line
+/- 4kV line-to-earth, +/- 2kV line-to-line
10V
10V
10V
10V
40 A/m continuous, 1000 A/m for 1 s
30% for 0.1s, 60% for 0.1s, 100% for 0.05s
30% for 1 period, 60% for 50 periods
100% for 5 periods, 100% for 50 periods 2
2.5kV common, 1kV diff. mode@1MHz
2.5kV common, 1kV diff. mode@1MHz
2.5kV common, 1kV diff. mode@1MHz
30V Continuous, 300V for 1s
30V Continuous, 300V for 1s
10%
2kVac (Fail-Safe Relay output)
2kVac
2kVac
5kV (Fail-Safe Relay output)
5kV
5kV
Test Levels
+/- 8kV
+/- 15kV
35 V/m
+/- 4kV @ 2.5kHz
+/- 4kV
+/- 4kV
+/- 4kV
2.5kV common mode @1MHz
2.5kV common, 1kV diff. mode@1MHz
2.5kV common, 1kV diff. mode@1MHz
5kV (Fail-Safe Relay output)
5kV
5kV
2kVac
2kVac
2kVac
Test Levels
Test Ad
-40°C, 16 Hours
Test Bd
+85°C, 16 Hours
95% (non-condensing), 55°C , 6
Test Db
cycles
Tests Fc
2g @ (10 - 150) Hz
Tests Ea
30g @ 11mS
Severity Levels
4
4
x
x
4
4
4
4
3
4
3
3
3
3
N/A
N/A
N/A
N/A
3
3
3
4
4
3
N/A
N/A
N/A
N/A
N/A
N/A
Severity Levels
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Severity Levels
N/A
N/A
N/A
Class 2
Class 2
RuggedVDSL
TM
RS930L
6

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ruggedvdsl rs930l

Table of Contents