4.2 IEEE 1613 Type Tests
IEEE 1613
IEEE Test
Clause
C37.90.3
9
C37.90.2
8
C37.90.1
7
C37.90.1
7
C37.90
6
C37.90
6
NOTE:
If the unit contains copper ports the IEEE 1613 conformance is Class 1 (During disturbance errors may occur
but recovery is automatic).
If the unit contains all fiber ports the IEEE 1613 conformance is Class 2 (During disturbance no errors will
occur).
4.3 IEC Environmental Type Tests
Test
IEC 60068-2-1
Cold Temperature
IEC 60068-2-2
Dry Heat
Humidity (Damp Heat,
IEC 60068-2-30
Cyclic)
IEC 60255-21-1
Vibration
IEC 60255-21-2
Shock
2010 RuggedCom Inc. All rights reserved
Description
Enclosure Contact
ESD
Enclosure Air
Radiated RFI
Enclosure ports
Signal ports
D.C. Power ports
Fast Transient
A.C. Power ports
Earth ground ports
Signal ports
Oscillatory
D.C. Power ports
A.C. Power ports
Signal ports
H.V. Impulse
D.C. Power ports
A.C. Power ports
Signal ports
Dielectric Strength
D.C. Power ports
A.C. Power ports
Description
Test Ad
Test Bd
Test Db
+/- 8kV
+/- 15kV
35 V/m
+/- 4kV @ 2.5kHz
+/- 4kV
+/- 4kV
+/- 4kV
2.5kV common mode @ 1MHz
2.5kV common & differential mode @ 1MHz
2.5kV common & differential mode @ 1MHz
5 kV (Failsafe Relay)
5 kV
5 kV
2kV AC(Failsafe Relay)
1.5kV DC
2kV AC
Test Levels
-40 deg. C, 16 Hours
+85 deg. C, 16 Hours
95% (non-condensing), 55°C, 6 cycles
2g @ (10-150) Hz
30g @ 11 ms
19
Test Levels
Severity
Levels
N/A
N/A
N/A
Class 2
Class 2
Rev105