Transferring The Ups Between Modes; Retrieving The Event Log; Setting Power Strategy - Avaya 9130 Installation And Operator's Manual

1000–3000 va uninterruptible power systems
Table of Contents

Advertisement

Transferring the UPS Between Modes

From Normal to Bypass Mode. Press any button to activate the menu
options, then select CONTROL and GO TO BYPASS.
From Bypass to Normal Mode. Press any button to activate the menu
options, then select CONTROL and GO TO NORMAL.

Retrieving the Event Log

To retrieve the Event Log through the display:
1.
2.
To retrieve the Event Log through the serial port:
1.
2.

Setting Power Strategy

On the High Efficiency setting, the UPS operates normally on Bypass,
transfers to inverter in less than 10 ms when utility fails, and transfers
back to Bypass in 1 minute after utility returns. The
illuminates when the UPS transfers to Bypass.
NOTE High Efficiency operation is available after one minute of stable power.
To set the power strategy:
1.
2.
Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator's Manual
Press any button to activate the menu options, then select
EVENT LOG.
Scroll through the listed events.
From the communication device connected to the serial port, send
one of the following command sequences: ESC-L (ASCII characters
27 and 76) or ESC-I (ASCII characters 27 and 108).
The UPS returns a header containing the UPS identification (UPS
type, part number, and serial number), firmware version, and the
current date and time, followed by the event history.
Use the connected communication device to view or print the
information. The report is delivered in ASCII format.
Press any button to activate the menu options, then select
SETTINGS, USER SETTINGS, and POWER STRATEGY.
Select HIGH EFFICIENCY or NORMAL, and ENTER to confirm.
OPERATION
indicator
S
43
164201765 Rev 1