Relay Output Contacts - Avaya 9130 Installation And Operator's Manual

1000–3000 va uninterruptible power systems
Table of Contents

Advertisement

COMMUNICATION
See Figure 14 on page 49 for REPO location. Figure 17 shows a
schematic of the REPO connector contacts.
You can set the REPO polarity. See the "REPO Input Polarity" setting in
"User Settings" on page 36.
NOTE Depending on user configuration, the pins must be shorted or open to keep the UPS
running. To restart the UPS, reconnect (re-open) the REPO connector pins and turn on the UPS
manually. Maximum resistance in the shorted loop is 10 ohm.
NOTE Always test the REPO function before applying your critical load to avoid accidental
load loss.

Relay Output Contacts

The UPS incorporates three programmable relay outputs with potential
free contacts for remote alarm indications: a standard relay port and two
outputs in the RS-232 communication port. See Figure 14 on page 49 for
the locations of the ports. An additional four relay outputs can be
obtained with the compatible Relay Interface Card.
Configure the relay outputs with the "Relay Configuration" setting in
"User Settings" on page 36.
54
Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator's Manual
+ Polarity
1
2
– Polarity
Figure 17. REPO Connections
REPO
S
164201765 Rev 1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents