Avaya RS9RM Preparation, Installation And Operator Manual

6000 va hardwired

Advertisement

Quick Links

Avaya RS9RM 6000 VA Hardwired
Uninterruptible Power Systems
Site Preparation,
Installation and Operator's Manual
www.powerware.com/avaya

Advertisement

Table of Contents
loading

Summary of Contents for Avaya RS9RM

  • Page 1 Avaya RS9RM 6000 VA Hardwired Uninterruptible Power Systems Site Preparation, Installation and Operator’s Manual www.powerware.com/avaya...
  • Page 3 Avaya RS9RM 6000 VA Hardwired Uninterruptible Power Systems Site Preparation, Installation and Operator’s Manual www.powerware.com/avaya...
  • Page 4 Avaya and the Avaya logo are trademarks of Avaya Inc. and may be registered in certain jurisdictions. Powerware, ABM, and LanSafe are registered trademarks and ConnectUPS is a trademark of Eaton Electrical Inc. Greenlee is a registered trademark of Greenlee Textron.
  • Page 5 Requesting a Declaration of Conformity Units that are labeled with a CE mark comply with the following harmonized standards and EU directives: Harmonized Standards: EN 50091-1-1 and EN 50091-2; IEC 60950 Third Edition EU Directives: 73/23/EEC, Council Directive on equipment designed for use within certain voltage limits 93/68/EEC, Amending Directive 73/23/EEC 89/336/EEC, Council Directive relating to electromagnetic compatibility 92/31/EEC, Amending Directive 89/336/EEC relating to EMC...
  • Page 6 Special Symbols The following are examples of symbols used on the UPS or accessories to alert you to important information: RISK OF ELECTRIC SHOCK - Indicates that a risk of electric shock is present and the associated warning should be observed. CAUTION: REFER TO OPERATOR’S MANUAL - Refer to your operator’s manual for additional information, such as important operating and maintenance instructions.
  • Page 7: Table Of Contents

    ............Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual...
  • Page 8 ................Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual...
  • Page 9 — causing hours of lost productivity and expensive repairs. With the Avaya RS9RM, you can safely eliminate the effects of power disturbances and guard the integrity of your equipment. Figure 1 shows the Avaya RS9RM UPS with an optional Extended Battery Module (EBM).
  • Page 10 Two additional communication options with a USB port and a DB-9 serial port. Advanced power management with the Software Suite CD for graceful shutdowns and power monitoring. Backed by worldwide agency approvals. Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 11: Important Safety Instructions

    Proper disposal of batteries is required. Refer to your local codes for disposal requirements. Never dispose of batteries in a fire. Batteries may explode when exposed to flame. Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 12 Korrekt bortskaffelse af batterier er påkrævet. Overhold gældende lokale regler for bortskaffelsesprocedurer. Skaf dig aldrig af med batterierne ved at brænde dem. Batterierne kan eksplodere ved åben ild. Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 13 Houd onbevoegden uit de buurt van de accu’s. De batterijen moeten op de juiste wijze worden opgeruimd. Raadpleeg hiervoor uw plaatselijke voorschriften. Nooit batterijen in het vuur gooien. De batterijen kunnen ontploffen. Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 14 Älä päästä valtuuttamatonta henkilöstöä lähelle akkuja. Akusto täytyy hävittää säädösten mukaisella tavalla. Noudata paikallisia määräyksiä. Älä koskaan heitä akkuja tuleen. Ne voivat räjähtää. Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 15 Pour les models l’onduleur ayant des sorties câblées, les interrupteurs de déconnexion convenables pour le(s) circuit(s) de sortie de courant alternatif doivent être fournie par un autre fournisseur. Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 16 Schmutzstoffen vorhanden sind. Die Umgebungstemperatur darf 40°C nicht übersteigen. Die USV nicht in der Nähe von Wasser oder in extrem hoher Luftfeuchtigkeit (max. 95 %) betreiben. Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 17: Avvisi Di Sicurezza

    La temperatura ambiente non deve superare i 40°C. Non utilizzare l’unità in prossimità di acqua o in presenza di umidità eccessiva (95% max). Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 18: Viktig Sikkerhetsinformasion

    Romtemperaturen må ikke overskride 40°C. Den må ikke brukes i nærheten av vann eller ved meget høy luftfuktighet (95% maks.). Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 19 A temperatura ambiente não deve exceder 40°C. Não opere próximo a água ou em umidade excessiva (máx: 95%). Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 20 Siga as instruções apropriadas ao desfazer-se das baterias. Consulte os códigos do local para maiores informações sobre os regulamentos de descarte de produtos. Nunca jogue as baterias no fogo, porque há risco de explosão. Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 21: Introduction

    устройство защиты от перегрузки выходного контура (контуров) переменного тока приобретается отдельно. Для моделей ИБП с постоянно запаянными выходными контактами соответствующие размыкающие переключатели выходного контура (контуров) переменного тока приобретаются отдельно. Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 22: Advertencias De Seguridad

    La temperatura ambiente no debe exceder los 40°C. No trabaje cerca del agua o con humedad excesiva (95% máximo). Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 23 är kontrollerade och där inga ledande föroreningar förekommer. Omgivande temperatur får ej överstiga 40°C. Använd inte utrustningen nära vatten eller vid hög luftfuktighet (max 95 %). Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 24 Håll ej behörig personal borta från batterierna. Batterierna måste avyttras enligt anvisningarna i lokal lagstiftning. Använda batterier får aldrig brännas upp. De kan explodera. Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 25: Installation

    NOTE Check the battery recharge date on the shipping carton label. If the date has expired and the batteries were never recharged, do not use the UPS. Contact your Avaya service representative. NOTE Inspect the battery trays for any loose connections. If any damage occurred during shipment, file a claim for concealed damage.
  • Page 26: Installing The Ups Internal Batteries

    Figure 3. Securing the Battery Trays Install the UPS front covers provided in the accessory kit (see Figure 4). Figure 4. Installing the UPS Front Covers Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 27: Tower Setup

    NOTE The EBM(s) must be installed to the right of the UPS as shown in Figure 5. Joining brackets are required for installations with two or more cabinets. Figure 5. Tower UPS with an EBM Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 28: Ebm Installation

    EBM. Repeat for each additional EBM. Up to four EBMs may be connected to the UPS. Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 29: Remote Emergency Power-Off Installation

    Connectors Figure 7. Typical EBM Installation Remote Emergency Power-off Installation The Avaya RS9RM includes a REPO connector that allows power to be switched off at the UPS output from a customer-supplied switch in a remote location. The REPO feature shuts down the protected equipment immediately and does not follow the orderly shutdown procedure initiated by any power management software.
  • Page 30 Figure 8. REPO Connector Verify that the externally-connected REPO switch is not activated to enable power to the UPS output. Continue to the following section, “Hardwired UPS Installation.” Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 31: Hardwired Ups Installation

    Single-phase 50/60 Hz The breaker must be wall-mounted and be readily accessible to the operator Flexible metal conduit (recommended for ease of service and maintenance) Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 32 Insert each conduit through a wiring access entry and attach the conduit fitting to the panel. Strip 1.5 cm (0.5I) of insulation from the end of each incoming wire. Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 33 2.5–16 mm L2/Neutral Out 1.8 Nm (16 lb in) (14–6 AWG) (14–6 AWG) Output Ground * Use 2.0 mm (14 AWG) 75_C copper wire minimum. Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 34 NOTE If you installed power management software and optional EBMs, ensure maximum battery runtime by using the Virtual Front Panel UPS utility on the Software Suite CD. Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 35: Configuration

    NOTE The UPS exits Configuration mode automatically after two minutes of inactivity. Press and hold the On button and the button simultaneously for three seconds to exit Configuration mode at any time. Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 36 Flashing Alarm DOES NOT sound when the polarity of the outlet (default) is reversed or the ground connection is missing. Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 37: Operation

    To turn on the UPS without using utility power, press and hold the On button for approximately three seconds. The UPS starts up in Battery mode and supplies battery power to your equipment. Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 38: Turning The Ups Off

    The UPS cycles the bar graph indicators twice, verifies the battery converter, and schedules the battery test to occur within 24 hours. Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 39: Transferring The Ups To Bypass Mode

    Bar Graph Indicators Battery Mode Indicator Bypass Mode Indicator Indicator Legend Unlit Test/Alarm Reset Button Flashing Off Button On Button Figure 12. UPS Front Panel Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 40: Normal Mode

    Figure 13. Load Level Indicators When all of the bar graph indicators are illuminated and the indicator flashes, power requirements exceed UPS capacity; see page 49 for more information. Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 41: Battery Mode

    If utility power returns before UPS shutdown, the UPS transfers to Normal mode operation while the battery recharges. If utility power returns after UPS shutdown, the UPS automatically restarts. Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 42: Bypass Mode

    UPS is in Standby mode. The indicator flashes and the bar graph indicators are off, indicating that power is not available to your equipment. The battery recharges when necessary. Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 43: Communication

    Connect the other end of the USB cable to the USB port on your computer. Install the Powerware LanSafe software and USB drivers according to the instructions provided with the Software Suite CD. Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 44: Db-9 Communication Port

    — No Connection — AC Fail AC Fail relay contact; 20 mA, 30 Vdc contact rating Power Source +V (8 to 24 volts DC power) Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 45: Connectups-X Web/Snmp Card

    Power LED (green) 100 Mb Status LED (yellow) Network LEDs (green) DIP Switch Additional Ethernet Connectors COM Port Reset Button Figure 17. ConnectUPS-X Panel Details Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 46 COMMUNICATION Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 47: Ups Maintenance

    UPS. Contact your Avaya service representative. When to Replace Batteries When the indicator flashes, the batteries may need replacing. Contact your Avaya service representative to order new batteries. Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 48: Replacing Batteries

    Switch the battery circuit breaker on the UPS rear panel to the OFF (O) position. Remove the lower UPS front cover (see Figure 18). Figure 18. Removing the Lower UPS Front Cover Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 49: Testing New Batteries

    The UPS cycles the bar graph indicators twice, verifies the battery converter, and schedules the battery test to occur within 24 hours. Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 50: Recycling The Used Battery Or Ups

    C A U T I O N Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center. Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 51: Specifications

    (Battery Mode) Voltage Waveform Normal mode: Sine wave; <3% THD with linear or PFC load; <6% with nonlinear load or SMPS UPS Output Connection Hardwired Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 52 17.4” 26.9” 5.1” (3U) × × 240 Vdc Extended Battery 64.8 71.6 71.4 cm 440 kg (970 lb) × × Cabinet (EBC240) 25.5” 28.2” 28.1” Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 53 121.9 178.0 237.4 2000 VA/1400W 37.7 107.5 186.2 271.4 361.6 NOTE Battery times are approximate and vary depending on the load configuration and battery charge. Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 54 SPECIFICATIONS Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 55: Troubleshooting

    (see Table 11). To silence the alarm for an existing fault, press the button. If UPS status changes, the alarm beeps, overriding the previous alarm silencing. Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 56 Warning - Low Battery Battery Modules (EBMs), the Low Battery warning may occur before the batteries reach 25% capacity. See Table 10 on page 45 for estimated runtimes. Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 57 If the overload condition persists, the UPS automatically 2 minutes; 112–150% for up to shuts down. 30 seconds) or the load is Overload defective. Continuous audible alarm Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 58: Obtaining Service

    Avaya RS9RM Hardwired PPDM 4-Post Rail Kit 700315138 700404734 Black 4-Post Rail Kit Seismic Kit 700315146 700404742 3-Unit Seismic Kit (1 UPS, 1 PPDM, and 1 EBM) Avaya RS9RM 6000 VA Hardwired UPS Site Preparation, Installation and Operator’s Manual 164201528 Rev C...
  • Page 60 *164201528C* 164201528 C...