Ups Startup And Shutdown; Starting The Ups - Avaya 9130 Installation And Operator's Manual

1000–3000 va uninterruptible power systems
Table of Contents

Advertisement

UPS Startup and Shutdown

To start up or shut down the UPS, see:
S
S
S

Starting the UPS

To start the UPS:
1.
2.
3.
4.
5.
6.
7.
Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator's Manual
"Starting the UPS" on page 41
"Starting the UPS on Battery" on page 42
"UPS Shutdown" on page 42
Verify that the UPS power cord is plugged in.
Switch on utility power where the UPS is connected.
The UPS front panel display illuminates and shows a status of "UPS
initializing . . ."
Verify that the UPS transfers to Standby mode ("UPS on standby").
Press the
button on the UPS front panel for at least one second.
The UPS front panel display changes status to "UPS starting . . ."
Check the UPS front panel display for active alarms or notices.
Resolve any active alarms before continuing. See
"Troubleshooting" on page 79.
If the
indicator is on, do not proceed until all alarms are clear.
Check the UPS status from the front panel to view the active
alarms. Correct the alarms and restart if necessary.
Verify that the
indicator illuminates solid, indicating that the
UPS is operating normally and any loads are powered.
The UPS should be in Normal mode.
ESC
Press the
button until the start screen appears.
OPERATION
S
41
164201765 Rev 1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents