Programmable Signal Inputs - Avaya 9130 Installation And Operator's Manual

1000–3000 va uninterruptible power systems
Table of Contents

Advertisement

The relay output contacts must not be connected to any utility connected circuits. Reinforced
insulation to the utility is required. The relay output contacts have a maximum rating of
30 Vac/1A and 60 Vdc/2A nominal values.
Table 5 shows the options for the relay output contacts.
Table 5. Relay Output Configuration Options
Signal
UPS ok
On Bypass
On Battery
Battery Low
Ext. Charger On
Figure 18 shows a schematic of the relay output contacts.

Programmable Signal Inputs

The UPS incorporates four programmable signal inputs: one RS-232
input, two connectivity card inputs, and one REPO terminal input. See
Figure 14 on page 49 for the locations of the ports. Configure the inputs
with the "Signal Inputs" setting in "User Settings" on page 36.
Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator's Manual
W A R N I N G
Description
Activated when the UPS is feeding the load on inverter or on
bypass and no alarms are active
Activated when the UPS is NOT on bypass operation
Activated when the UPS operates on battery and the "On
Battery Notice Delay" time has expired
Activated with the "Battery Low" alarm according to the
"Battery Low Alarm" setting
Controls an optional external battery charger on and off
1
Normally Open
Normally Closed
2
3
Common
Figure 18. Standard Relay Port Connections