Page 1
Site Preparation, Installation and Operator’s Manual Avaya Avaya Series 1 Uninterruptible Power Systems Models 4500/5000/6000 VA Select Code 167-405-115...
Page 2
Novell is a registered trademark of Novell, Inc. 3Com is a registered trademark of 3Com Corporation. C opyright 2001 Avaya Inc. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Avaya Inc.
Page 3
Site Preparation, Installation and Operator’s Manual Avaya Avaya Series 1 Uninterruptible Power Systems Models 4500/5000/6000 VA Select Code 167-405-115 Issue 5 Copyright 2001 Avaya Inc. All Rights Reserved...
Page 4
Special Symbols The following are examples of symbols used on the UPS to alert you to important information: LOAD ON – Press the button with this symbol to energize the output receptacles (Output On). – Press the button with this symbol to de-energize the output LOAD OFF receptacles (Output Off).
Page 5
BDM Q WITH UICK NSTALLATION C A U T I O N Read the safety instructions beginning on page 5 before installing the UPS. Desired Output Voltage Selector Position Voltage 100/200V 110/220V 115/230V 120/240V 208 if UPS Input is 208V 240 if UPS Input is 240V...
C H A P T E R 1 NTRODUCTION Congratulations on the purchase of your Avaya Series 1 uninterruptible power system (UPS). The UPS meets the toughest measures of superior design and manufacturing, including ISO 9001. You now own the most reliable power protection available.
Page 10
Introduction Figure 1. Model 6000 UPS Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
Battery times NOTE Do not connect more than six standard battery modules to the PPU. For extended battery times, contact your Avaya Inc. representative. Load Requirements The load is the equipment to be protected by the UPS. Select the UPS model that meets the power consumption requirements of the load in volt-amperes (VA).
The on/off switch on the UPS does not electrically isolate the internal parts. Unplug the input cord from the wall outlet when disconnecting the unit for long periods of time. Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
Page 14
Installér denne UPS i et temperatur- og fugtighedskontrolleret indendørsmiljø, frit for ledende forureningsstoffer for at formindske risikoen for brand og elektrisk stød. Rumtemperaturen må ikke overstige 40°C. UPS’en bør ikke betjenes nær vand eller høj fugtighed (maksimalt 95%). Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
De batterijen moeten op de juiste wijze worden opgeruimd. Raadpleeg hiervoor uw plaatselijke voorschriften. Deze UPS bevat zijn eigen energiebron (batterijen). De uitgangsaansluitingen kunnen onder spanning staan wanneer de UPS niet op een wisselstroom voeding is aangesloten. Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
Page 16
Voor Bypass Module systemen met vast-bedrade uitgangen, moet de overstroombeveiliging voor wisselstroom uitgangcircuit(s) door derden worden geleverd. Voor Bypass Module systemen met vast-bedrade uitgangen, moeten de juiste hoofdschakelaars voor wisselstroom uitgangcircuit(s) door derden worden geleverd. Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
Page 17
UPSin lähtöteho PÄÄLLÄ -painiketta ( ), riippumatta siitä, onko tulokaapeli kytkettynä tai ei. Palovaaran vähentämiseksi UPS ja ohituslaite tulee kytkeä virtapiiriin, jonka haaroitusjohtojen ylivirtasuojauksen maksimiarvo on 30 A. Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
Page 18
(95 % maximum). Ne pas retirer le cordon d’alimentation lorsque l’onduleur est sous tension sous peine de supprimer la mise à la terre de l’onduleur et du matériel connecté. Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
Page 19
Diese USV ist mit einer eigenen Energiequelle (Batterie) ausgestattet. An den Ausgangssteckdosen kann auch dann Spannung anliegen, wenn die USV nicht an einer Wechselspannungsquelle angeschlossen ist. Batterien niemals verbrennen, da sie explodieren können. Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
Page 20
Für Bypass-Systeme mit festverdrahteten Eingängen muß der Überstromschutz für die Ausgangswechselstromkreise anderweitig bereitgestellt werden. Für Bypass-Systeme mit festverdrahteten Ausgängen müssen Trennschalter für die Ausgangswechselstromkreise mit passendem Nennwert anderweitig bereitgestellt werden. Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
Page 22
Le batterie possono presentare rischio di scossa elettrica o di ustioni provocate da alta corrente dovuta a corto circuito. Osservare le apposite istruzioni. Le batterie devono essere smaltite in modo corretto. Per i requisiti di smaltimento fare riferimento alle disposizioni locali. Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
Page 23
Nei sistemi Bypass provvisti di uscite cablate, i sezionatori di corrente nominale adeguata per il/i circuito/i a corrente alternata in uscita devono essere forniti da terzi. Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
Page 24
For BDM systemer med fastkoplete uttak, må overstrømvern for vekselstrømuttak(ene) stilles til rådighet av andre. For BDM systemer med fastkoplete uttak, må passende utkoplingsbrytere for vekselstrømuttak(ene) stilles til rådighet av andre. Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
Page 25
à presença de energia elétrica na rede de alimentação. Para reduzir o risco de incêndios, conecte a UPS somente a um circuito com proteção de sobrecarga de derivação de no máximo 30 ampères. Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
Page 26
Никогда не бросайте аккумуляторы в огонь. Аккумуляторы могут взорваться под воздействием огня. Никогда не открывайте и не деформируйте аккумуляторы. Вытекающий электролит опасен для кожи и глаз, и может быть крайне токсичным. Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
Page 27
по току выходной(ых) цепи(ей) переменного тока должна обеспечиваться сторонними организациями. Для блока байпаса с неразъемными выходами сторонними организациями должны быть обеспечены выключатели выходной(ых) цепи(ей) переменного тока, рассчитанные на соответствующий номинал. Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
El interruptor de encendido/apagado del SIE no tiene aislación eléctrica de las partes internas. Desenchufe el cable de entrada del tomacorriente de la pared cuando desconecte la unidad durante períodos largos. Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
Page 29
UPS-enhet inomhus, där temperatur och luftfuktighet är kontrollerade och där inga ledande föroreningar förekommer. Omgivande temperatur får ej överstiga 40 ° Använd inte utrustningen nära vatten eller vid hög luftfuktighet (max 95 %). Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
Page 30
Överströmsskydd för de utgående växelströmkretsarna ska tillhandahållas av andra för fast anslutna förbikopplingssystem. Strömbrytare för bortkoppling med passande dimensioner för de utgående växelströmkretsarna ska tillhandahållas av andra för fast anslutna förbikopplingssystem. Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
Call Center, Conversant, or Voice Processing that use a Remote Management Board require an isolated contact-closure interface that is provided by a special UPS Alarm Interface Adapter (PEC 24433). Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
NOTE Do not connect more than six standard battery modules to the PPU. For extended battery times, contact your Avaya representative. Do not place more than six modules in one stack (the PPU is equal to two modules and the BDM is equal to two modules).
Page 33
(the smaller flanges without holes face toward the front) Battery Modules 1/4-20 x 1/2 Screws Caster Base Floor Mounting Plate 1/4-20 x 1/2 Screws Figure 3. UPS with BDM Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
Page 34
(not provided). Secure the plate to the floor. WALL 11.0 minimum recommended for cabling Seismic Mounting Holes 16.16 10.0 Unit Depth FRONT 12.5 Unit Width Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
Page 35
7. Verify the Bypass switch on the BDM rear panel is in the NORMAL position (see Figure 5 on page 29). 8. Verify the circuit breaker on all battery modules is in the OFF (O) position (see Figure 4). Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
Page 36
568 mm (22.35 Serial Port Input Plug Input Breaker Output Receptacle Voltage Selector Switch REPO Receptacle Depth of Unit: 406 mm (16 Figure 4. UPS with Battery Modules (Rear View) Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
Page 37
Set to 220V for 110/220V BDM output Set to 230V for 115/230V BDM output Set to 240V for 120/240V BDM output *The UPS output voltage must match input voltage. Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
Page 38
Plug the equipment into the power output receptacles on the BDM rear panel. Skip to Step 20 on page 34 to connect the battery module(s). 14. Connect additional equipment to the EPDM, if one is installed. Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
Page 39
16. Hardwire the input (TB1) and output terminations (TB2) for the BDM. See the following hardwired terminations table for specifications. See Figure 8 and Figure 9 on page 33 for a detailed view of the terminal blocks. Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
Page 40
200V, 220V, 200V, 220V, 200V, 220V, 200V, 220V, TB2 2 and TB2 3 TB2-2 and TB2-3 TB2 1 and TB2 4 TB2-1 and TB2-4 230V, or 240V 230V, or 240V Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
Page 42
Follow this procedure for each additional battery module. 22. Remove the breaker tie from the circuit breaker on all battery modules. Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
3. Pivot the REPO receptacle guard out of the way, plug the REPO plug/receptacle PPU connector into the REPO receptacle on the PPU rear panel and twist the connector in place (see Figure 4 on page 28). Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
Page 44
(see the following table). Tighten the compression terminals with a screwdriver (see Figure 11). Mounting Holes Plug/Receptacle PPU Connector Access Hole for Conduit Three Foot Cord Terminal Block Figure 11. Optional REPO Cord Junction Box Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
NEC specifications or national wiring rules (see Figure 12 for an example). See “Specifications” on page 61 for the input current/output voltage requirements. Phase 1 208/220/230/240V Phase 2/Neutral (International) Ground Figure 12. L6-30 Receptacle Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
Page 46
To restart the UPS, follow the startup procedure beginning on page 37. NOTE If the REPO test fails and the UPS does not shutdown, contact your service representative. Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
UPS for approximately 8 hours to ensure the battery is fully charged and full backup time is available. If the I3 indicator flashes, operate the UPS for 24 hours to charge the battery. Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
O U T P U T O N On Battery or Bypass O N B A T T E R Y Indicator O R B Y P A S S Figure 13. UPS Front Panel Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
LOAD ON LOAD ON LOAD ON LOAD ON LOAD OFF APPROX. APPROX. APPROX. APPROX. NORMAL 81-100% 61-80% 41-60% 0-40% UTILITY LOAD LOAD LOAD LOAD Figure 15. Normal Operation Indicators Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
If battery capacity becomes low while in Battery mode, the I3 indicator begins to flash and the Output On indicator remains lit, indicating approximately two minutes before UPS shutdown. The alarm beeps every two seconds. Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
The UPS supplies power to your equipment and goes into Battery mode. indicator remains lit and the front panel displays the percentage of battery capacity remaining to the UPS. This process should take about 15 seconds. Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
1. Perform a UPS shutdown as described in the previous section. 2. Select the new voltage (see Step 9 on page 29). 3. Restart the UPS by performing a UPS startup as described on page 37. Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
The UPS enters Battery mode for several seconds. The µ i ndicator turns off and the UPS shuts down. 4. Remove the cord connections to the back of the PPU. Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
Page 56
Do not turn the Voltage Selector switch while the UPS is operating (see “Changing the Output Voltage” on page 45). Changing the output voltage while the UPS is operating may cause an emergency power-off. Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
Page 57
7. Turn the Bypass switch on the BDM to the NORMAL position. The front panel displays the percentage of full load being applied to the UPS. The UPS is now in Normal mode with the load online. Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
Use the Display Configuration option on the UPS Serial Communications Menu (see page 54). If you want to change the UPS configuration settings, use the front panel or the UPS Serial Communications Menu. Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
) ) ) ) , , , , N N N N o o o o v v v v e e e e l l l l l l l l C C C C o o o o n n n n t t t t a a a a c c c c t t t t s s s s OVERLOAD OVERLOAD OUTPUT ON OUTPUT ON Figure 21. Front Panel Communication Options Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
Page 61
6. Press the Output On button again to return the UPS to Normal mode. NOTE Printer mode selections are the only serial communication modes available from the front panel. Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
D > Display Configuration settings and the new settings that you have selected prior to saving them. The new settings are not effective until you select save from the Main Menu. Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
Page 63
The UPS prints the formatted data on the P > Printer Dump attached printer. allows you to configure the UPS for a new L > LAN Configuration LAN mode and displays the Select LAN Configuration Menu. Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
Page 64
T O Q U I T T H I S M E N U E N T E R S E L E C T I O N > = > Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
UPS serial port. The connector body and style may vary as well. Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
Page 66
50 feet (15m). See Figure 22 for the location of the serial port. UPS Rear Panel Serial Port Serial Port Detail Figure 22. Serial Port Location Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
Pin numbers separated by a forward slash ( / ) are connected together internally. N N N N O O O O T T T T E E E E Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
Page 68
Communication Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
Plug/Receptacle: 406 mm (16 400 mm (15.75 Plug/Receptacle: 406 mm (16 Hardwired: 463 mm (18.25 Hardwired: 463 mm (18.25 Weight 18 kg (39 lb) 23.6 kg (52 lb) 37 kg (82 lb) Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
Temperature: 10 C to 40 ° ° F to 104 ° ° Humidity: 5 to 95% (noncondensing) Agency Approvals Safety: EN50091-1 UL 1778 EMC: FCC Part 15 Class A EN50091-2 Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
Input and output currents are approximately the same when load is powered through bypass. N N N N O O O O T T T T E E E E Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
Page 73
Input and output currents are approximately the same when load is powered through bypass. N N N N O O O O T T T T E E E E Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
Verify cable integrity (see page 57). function properly. Incorrect baud rate. Select a new baud rate (see page 57). Incorrect communication mode. Select a new communication mode (see Chapter 5). Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
Page 76
Verify that the battery module breaker is in the OUTPUT ON ON ( ) position. Battery module is not properly Verify that the battery cords are connected. connected to the UPS. Avaya Model 6000 UPS Operator’s Manual 167-405-115 Issue 5 Uncontrolled Copy...
The troubleshooting chart on page 67 covers most of the difficulties you may encounter during normal operations. If you have any questions or problems with your UPS, call your Avaya service representative or the appropriate telephone number on the service label of your UPS.