3000 va, 120v uninterruptible power systems

Advertisement

Avaya S9RM 3000 VA, 120V Uninterruptible Power Systems
Site Preparation,
Installation and Operator's Manual
Material Code 700285596
www.avayaups.com

Advertisement

Table of Contents
loading

Summary of Contents for Avaya S9RM

  • Page 1 Avaya S9RM 3000 VA, 120V Uninterruptible Power Systems Site Preparation, Installation and Operator’s Manual Material Code 700285596 www.avayaups.com...
  • Page 3 Avaya S9RM 3000 VA, 120V Uninterruptible Power Systems Site Preparation, Installation and Operator’s Manual Material Code 700285596 Issue 1 Copyright 2003 Avaya Inc. All Rights Reserved...
  • Page 4: Special Symbols

    ABM are registered trademarks and ConnectUPS is a trademark of Powerware Corporation. Microsoft is a registered trademark of Microsoft Corporation. Netscape is a trademark of Netscape Communications Corporation. Copyright 2003 Avaya Inc. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Avaya Inc.
  • Page 5: Table Of Contents

    ............Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual...
  • Page 6 ..............Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual...
  • Page 7: Avaya S9Rm - The Ultimate Online Ups

    — causing hours of lost productivity and expensive repairs. With the Avaya S9RM, you can safely eliminate the effects of power disturbances and guard the integrity of your equipment. Figure 1 shows the Avaya S9RM UPS with an optional Extended Battery Module (EBM).
  • Page 8 : Flash memory provides easy upgrades or reconfiguration capability without requiring a service call. : The Avaya S9RM is backed by worldwide agency approvals. Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 9: Safety Warnings

    To comply with international standards and wiring regulations, the total equipment connected to the output of this UPS must not have an earth leakage current greater than 1.5 milliamperes. Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 10 I overensstemmelse med internationale normer og bestemmelser for el-installation må det udstyr, der er forbundet til udgangen af denne UPS, tilsammen ikke overskride en jordafdelingsspænding på mere end 1,5 milliampere. Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 11: Belangrijke Veiligheidsinstructies

    Om aan de internationale normen en bedradingsvoorschriften te voldoen mag de gehele apparatuur die op de uitgang van deze UPS is aangesloten, geen aardlekstroom van meer dan 1,5 milliampère hebben. Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 12 Ympäristön lämpötila ei saa ylittää 40 • C. Älä käytä lähellä vettä ja vältä kosteita tiloja (95 % maksimi). Kansainväliset normit ja johdotusmääräykset vaativat, että kaikkien tämän UPS-laitteen ulostulokytkentöjen yhteinen maavuotovirta ei ylitä 1,5 milliampeeria (mA). Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 13 Afin d’être conforme aux normes et règlements internationaux de câblage, le courant de fuite à la terre de la totalité du matériel branché sur la sortie de l’onduleur ne doit pas dépasser 1,5 mA. Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 14 Um internationale Normen und Verdrahtungsvorschriften zu erfüllen, dürfen die an den Ausgang dieser USV angeschlossenen Geräte zusammen einen Erdschlußstrom von insgesamt 1,5 Milliampere nicht überschreiten. Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 15 áãþãéìá õëéêÜ. Ç èåñìïêñáóßá ðåñéâÜëëïíôïò äåí ðñÝðåé íá îåðåñíÜåé ôïõò 40 C. Ìç ÷ñçóéìïðïéåßôå ôï UPS êïíôÜ óå íåñü Þ • õðåñâïëéêÞ õãñáóßá (ìÝãéóôç ôéìÞ: 95%). Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 16: Avvisi Di Sicurezza

    è acceso poichè in tal modo si disattiverebbe il collegamento a terra di sicurezza del gruppo statico di continuità e dell’apparecchiatura ad esso collegata. Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 17: Viktig Sikkerhetsinformasion

    Romtemperaturen må ikke overskride 40 • C. Den må ikke brukes i nærheten av vann eller ved meget høy luftfuktighet (95% maks.). Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 18 Para estar de acordo com os padrões internacionais e os regulamentos de fiação, o equipamento total conectado à saída desta UPS não deve ter uma corrente de fuga à terra maior que 1,5 miliampères. Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 19 отсутствуют проводящие загрязняющие вещества. Температура окружающего воздуха не должна превышать 40 • С. Не эксплуатируйте устройство около воды или в местах с повышенной влажностью (макс. 95%). Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 20: Advertencias De Seguridad

    No retire o desenchufe el cable de entrada mientras el SIE se encuentre encendido. Esto suprime la descarga a tierra de seguridad del SIE y de los equipos conectados al SIE. Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 21 UPS-enheten inte är ansluten till en växelströmkälla. Ta aldrig bort nätsladden när UPS-enheten är påslagen. Detta tar bort skyddsjordningen från både UPS-enheten och den anslutna utrustningen. Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 22 Batterierna kan ge elektriska stötar eller brännskador från hög kortslutningsström. Följ tillämpliga anvisningar. Batterierna måste avyttras enligt anvisningarna i lokal lagstiftning. Använda batterier får aldrig brännas upp. De kan explodera. Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 23: Installation

    Avaya service representative. UPS Setup The Avaya S9RM UPS is designed for flexible configurations and can be installed in a rack or as a standalone cabinet. If you are installing the UPS in a rack, continue to the following section “Rack-Mount Setup;”...
  • Page 24: Rack-Mount Setup

    NOTE Mounting rails are required for each individual cabinet. If rails are not already installed in your rack, contact your Avaya sales representative to order rail kit(s). Use the following procedure to install the UPS in a rack: 1.
  • Page 25: Tower Setup

    3. Position the pedestals over the end of the UPS cabinet so that the weight of the unit is evenly distributed. Secure the pedestals with the screws provided in the accessory kit. Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 26 NOTE The PDM must be installed to the left of the UPS and the EBM(s) must be installed to the right of the UPS as shown in Figure 8. Figure 6. Installing Pedestals on the Left Cabinet Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 27 UPS as shown in Figure 8. Air Vents PDM and UPS UPS and EBM Figure 8. Pedestals with Two Cabinets Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 28 Figure 10. Installing the Joining Brackets (Top View with Pedestals) 10. If installing additional cabinets, repeat Step 9 for each cabinet. 11. Continue to the following section, “EBM Installation.” Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 29: Ebm Installation

    EBM. Repeat for each additional EBM. Up to four EBMs may be connected to the UPS. 4. Continue to the following section, “Power Connections.” Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 30 Installation UPS Battery Connector EBM Cable EBM Battery Connectors Figure 12. EBM Installation Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 31: Power Connections

    5. If an emergency power-off (disconnect) switch is required by local codes, see “Remote Emergency Power-Off” on page 27 to install the REPO switch before powering on the UPS. Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 32 NOTE The batteries charge to 90% capacity in approximately 3 hours. However, it is recommended that the batteries charge for 24 hours after installation or long-term storage. Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 33: Remote Emergency Power-Off

    Installation Remote Emergency Power-Off The Avaya S9RM includes a REPO port that allows power to be switched off at the UPS output receptacles from a customer-supplied switch in a remote location. The REPO feature shuts down the protected equipment immediately and does not follow the orderly shutdown procedure initiated by any power management software.
  • Page 34: Ups Rear Panel

    Network Transient Protector Two 5-20 Receptacles Circuit Protector Two 5-15 Receptacles Power Cord with L5-30P L5-30 Receptacle Figure 16. S9RM 3000 VA, 120V Rear Panel Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 35: Operation

    If you do not unplug the UPS, it remains in Standby mode. Pressing the Off button while the UPS is in Battery mode causes the UPS to shut down immediately. Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 36: Initiating The Self-Test

    Bar Graph Indicators Battery Mode Indicator Bypass Mode Indicator Indicator Legend Unlit Test/Alarm Reset Button Flashing Off Button On Button Figure 17. UPS Front Panel Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 37: Normal Mode

    10%. Each LED represents 1/4 of a full load rating. When all of the bar graph indicators are illuminated and the indicator flashes, power requirements exceed UPS capacity; see page 57 for more information. Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 38: Battery Mode

    When utility power is restored after the UPS shuts down, the UPS automatically restarts. Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 39: Bypass Mode

    ( ˆ 10%), the UPS shuts down the load. This feature conserves battery power. To enable this feature, contact your service representative. Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 40 Operation Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 41: Configuration

    If you press the On button and nothing happens, the UPS is still in Operation mode. Repeat Step 1 for one beep ONLY to enter Configuration mode, and then perform Step 2. Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 42 Configuration and Operation mode. Test/Alarm On Button Reset Button Press the On button to scroll to the next option. Figure 20. Using the Configuration Mode Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 43 AC Input Failure Alarm On (default) Alarm sounds when there is an AC input failure. Flashing Alarm DOES NOT sound when there is an AC input failure. Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 44 Configuration Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 45: Additional Ups Features

    Power LED (green) 100 Mb Status LED Network (yellow) LEDs (green) DIP Switch Additional Ethernet Connectors COM Port Reset Button Figure 21. ConnectUPS-X Panel Details Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 46: Network Transient Protector

    IN. 2. Connect the network or telephone cable (low voltage units only) to the jack labeled OUT. Figure 22. Network Transient Protector Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 47: Load Segments

    PDM Bypass switch is returned to the NORMAL position. Load Segment 1 Load Segment 2 Figure 23. UPS Load Segments for S9RM 3000 VA, 120V Models Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 48 Additional UPS Features Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 49: Ups Maintenance

    (it may take a few seconds to turn off). If the indicator stays on, contact your Avaya service representative to order new batteries. Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 50: Replacing Batteries

    5. Replace the EBM. See “Recycling the Used Battery” on page 48 for proper disposal. 6. Reinstall the pedestals if removed in Step 3. 7. Reinstall the EBM brackets if removed in Step 2. Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 51 Plug the EBM cable into the battery connector on the adjacent EBM. Brackets EBM Battery Connectors EBM Cables UPS Battery Connector Figure 25. EBM Connections Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 52: How To Replace Internal Batteries

    2. Push down and unsnap the LED panel. 3. Disconnect the battery cable from the UPS and cut the battery cable wire tie. Battery Cable LED Panel Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 53: Testing New Batteries

    (it may take a few seconds to turn off). If the indicator stays on, check the battery connections. Call your Avaya service representative if the problem persists. Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 54: Recycling The Used Battery

    PDM rear panel. See Figure 26. 5. Disconnect the UPS power cord from the UPS-input connector on the PDM rear panel. 6. Remove the UPS. Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 55 UPS-Output Connector PDM Power Cord Bypass Switch Output Receptacles (Six 5-20R) UPS Power Cord UPS Battery Connector UPS Output Receptacle (L5-30) Figure 26. Power Connections Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 56 UPS Maintenance Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 57: Specifications

    17.0” x 23.9” x 3.5” (2U) (WxDxH) (43.2 x 60.7 x 8.9 cm) (43.2 x 60.7 x 8.9 cm) Weight 81.5 lb (37 kg) 93 lb (42.5 kg) Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 58 IEEE C62.41 Category B (formerly IEEE 587) Safety Conformance UL 1778, UL 497A; CSA C22.2, No. 107.1, 107.2; NOM-019-SCFI Agency Markings UL, cUL, NOM-NYCE EMC (Class A) FCC Part 15, ICES-003 Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 59 3 EBMs 4 EBMs Batteries 3000 VA/2100W 5/13 25/55 38/72 54/120 70/160 Battery times are approximate and vary depending on the load configuration and battery charge. Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 60 Specifications Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 61: Troubleshooting

    Silencing an Audible Alarm To silence the alarm for an existing fault, press the button. If UPS status changes, the alarm beeps, overriding the previous alarm silencing. Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 62 Three minutes or less of battery power remains (depending on load configuration and battery charge). Prepare for a shutdown. Save your work and turn off your Warning - Low Battery equipment. Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 63 5 seconds until all LEDs are off and restart the UPS. defective. If the overload condition persists (101–110% for 2 minutes Overload or 111–150% for 30 seconds), the UPS automatically shuts Continuous audible alarm down. Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 64: Obtaining Service

    700285281 Avaya S9RM 3K PDM2-LV-US-P1 Seismic Kit - 4 Slot 700285315 4-Slot Seismic Mounting Kit Seismic Kit - 6 Slot 700285323 6-Slot Seismic Mounting Kit Avaya S9RM 3000 VA, 120V UPS Site Preparation, Installation and Operator’s Manual 700285596 Issue 1...
  • Page 66   164201478 A...