Avaya 9135 6000 VA Installation And Operator's Manual
Avaya 9135 6000 VA Installation And Operator's Manual

Avaya 9135 6000 VA Installation And Operator's Manual

Advertisement

Quick Links

Avaya 9135 6000 VA
Uninterruptible Power Systems
Site Preparation,
Installation and Operator's Manual
www.powerware.com/avaya

Advertisement

Table of Contents
loading

Summary of Contents for Avaya 9135 6000 VA

  • Page 1 Avaya 9135 6000 VA Uninterruptible Power Systems Site Preparation, Installation and Operator’s Manual www.powerware.com/avaya...
  • Page 3 Avaya 9135 6000 VA Uninterruptible Power Systems Site Preparation, Installation and Operator’s Manual www.powerware.com/avaya...
  • Page 4 Phone: +358-9-452 661 Fax: +358-9-452 665 68 Avaya and the Avaya logo are trademarks of Avaya Inc. and may be registered in certain jurisdictions. Eaton and LanSafe are registered trademarks and ConnectUPS is a trademark of Eaton Corporation or its subsidiaries and affiliates.
  • Page 5 Class A EMC Statements FCC Part 15 This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to NOTE part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment.
  • Page 6 Special Symbols The following are examples of symbols used on the UPS or accessories to alert you to important information: RISK OF ELECTRIC SHOCK - Observe the warning associated with the risk of electric shock symbol. CAUTION: REFER TO OPERATOR’S MANUAL - Refer to your operator’s manual for additional information, such as important operating and maintenance instructions.
  • Page 7: Table Of Contents

    ..............Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual...
  • Page 8 ................Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual...
  • Page 9: Introduction

    — causing hours of lost productivity and expensive repairs. With the Avaya 9135, you can safely eliminate the effects of power disturbances and guard the integrity of your equipment. Figure 1 shows the Avaya 9135 UPS.
  • Page 10 Two standard communication options with a USB port and an RS-232 serial port. Advanced power management for graceful shutdowns and power monitoring. Network Management Card for increased power protection and control. Backed by worldwide agency approvals. Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 11: Safety Warnings

    To reduce the risk of fire or electric shock, install this UPS in a temperature and humidity controlled, indoor environment, free of conductive contaminants. Ambient temperature must not exceed 40°C (104°F). Do not operate near water or excessive humidity (95% maximum). Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 12 Rumtemperaturen må ikke overstige 40°C. UPS’en bør ikke betjenes nær vand eller høj fugtighed (maksimalt 95%). Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 13: Belangrijke Veiligheidsinstructies

    Verwijder de ingangsnoer niet of haal de stekker van de ingangsnoer er niet uit terwijl de UPS aan staat. Hierdoor zou de UPS en uw aangesloten apparatuur geen aardebeveiliging meer hebben. Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 14 Nooit batterijen in het vuur gooien. De batterijen kunnen ontploffen. Vervang de accu’s door accu’s met hetzelfde nummer en van hetzelfde type als de oorspronkelijke accu’s in de UPS. Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 15 Akusto täytyy hävittää säädösten mukaisella tavalla. Noudata paikallisia määräyksiä. Älä koskaan heitä akkuja tuleen. Ne voivat räjähtää. Vaihda UPS-virtalähteeseen vain samanlaiset akut ja sama määrä akkuja kuin siinä oli alun perin. Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 16 La température ambiante ne doit pas dépasser 40 °C. Ne pas utiliser à proximité d’eau ou dans une atmosphère excessivement humide (95 % maximum). Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 17 Ausgangssteckverbindern 0 Volt. Bei einer Verkabelung mit Außenleitern beträgt die Spannung an den Ausgangssteckverbindern 110–120 Volt (gemessen von Leitung zu Masse oder Leitung zu Masseleiter, abhängig von der UPS (USV)-Verkabelung. Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 18 Die Batterien müssen ordnungsgemäß entsorgt werden. Hierbei sind die örtlichen Bestimmungen zu beachten. Batterien niemals verbrennen, da sie explodieren können. Falls Sie die Batterien austauschen, verwenden Sie bitte ausschließlich die gleiche Anzahl und die Batterietypen. Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 19 La temperatura ambiente non deve superare i 40°C. Non utilizzare l’unità in prossimità di acqua o in presenza di umidità eccessiva (95% max). Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 20 Non gettare mai le batterie nel fuoco poichè potrebbero esplodere se esposte alle fiamme. Sostituire le batterie con altre dello stesso numero e tipo di quelle originariamente installate nell’UPS. Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 21 Batterier må fjernes på korrekt måte. Se lokale forskrifter vedrørende krav om fjerning av batterier. Kast aldri batterier i flammer, da de kan eksplodere, hvis de utsettes for åpen ild. Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 22 Mantenha o pessoal não autorizado afastado das baterias. Siga as instruções apropriadas ao desfazer-se das baterias. Consulte os códigos do local para maiores informações sobre os regulamentos de descarte de produtos. Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 23 температурой и влажностью, в котором отсутствуют проводящие загрязняющие вещества. Температура окружающего воздуха не должна превышать 40°С. Не эксплуатируйте устройство около воды или в местах с повышенной влажностью (макс. 95%). Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 24: Advertencias De Seguridad

    No retire o desenchufe el cable de entrada mientras el SIE se encuentre encendido. Esto suprime la descarga a tierra de seguridad del SIE y de los equipos conectados al SIE. Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 25 Europa) är spänningen till de utgående uttagen 0 V. Är den ingående strömkällan kopplad ledare-till-ledare är spänningen i de utgående uttagen 115 V (uppmätt från ledare-till-jord eller ledare-till-nolla beroende på UPS:ens anslutning). Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 26 Batterierna måste avyttras enligt anvisningarna i lokal lagstiftning. Använda batterier får aldrig brännas upp. De kan explodera. Byt ut batterierna mot samma antal och typer av batterier som ursprungligen installerats i UPS-enheten. Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 27: Installation

    15 days to your Avaya service representative. NOTE Check the battery recharge date on the shipping carton label. If the date has expired and the batteries were never recharged, do not use the UPS. Contact your Avaya service representative.
  • Page 28: Checking The Accessory Kit

    Description UPS user’s guide or CD Screwdriver RS-232 serial cable Rackmounting kit for 19-inch (48 cm) bays Two sets of pedestals with screws for tower position Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 29 EBM user’s guide EBM cable EBM communication cable Rackmounting kit for 19-inch (48 cm) bays Pedestal extenders for tower position Joining bracket and screws for tower position Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 30: Connecting The Ups Internal Battery

    Slide the battery connector so that you can read Connected (see Figure 3). Reinstall the two screws removed in Step 2. Figure 3. Connecting the Internal Battery Connector Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 31: Ups Setup

    INSTALLATION UPS Setup The Avaya 9135 UPS is designed for flexible configurations and can be installed in a rack or as a standalone cabinet. If you are installing the UPS in a rack, continue to the following section, “Rackmount Setup;” otherwise, continue to “Tower Setup” on page 30.
  • Page 32: Installing The Rail Kit

    DO NOT install the UPS or EBM in a hermetically-closed environment without any exchange of air. The UPS and EBM are heavy (see page 61): 1) Avaya strongly recommends to remove the battery tray from the UPS before lifting. 2) A minimum of two people are required to lift the cabinets into the rack.
  • Page 33 Place the front panel above the UPS. Remove the two battery retaining brackets (four screws). Slightly pull the battery tray, then lift it to extract it. Figure 5. Removing the Battery Tray Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 34 M4 6 mm flat-head screws. If installing additional cabinets, repeat Steps 3 and 4 for each cabinet. Figure 6. Installing the Mounting Brackets Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 35 Secure the rail to the front of the rack with two M6 12 mm screws. 10. Repeat Steps 8 and 9 for the other rail. Figure 7. Installing the Rails Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 36 13. Secure the front of the cabinet to the rack using two M6 12 mm round-head screws on each side (see Figure 9). Figure 9. Installing the Cabinets Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 37 15. If you removed the UPS battery tray in Step 2, replace the battery tray and secure with the battery retaining brackets. Replace the UPS front cover. 16. Continue to “Installing the UPS” on page 35. Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 38: Tower Setup

    (see Figure 12). Adjust the pedestals to the size of the UPS and secure the pedestals with the captive screws. Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 39 INSTALLATION UPS Indicators 150 mm (6”) 450 mm (17.7”) Figure 12. Tower Position with One Cabinet Continue to “Installing the UPS” on page 35. Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 40 For three cabinets or more, insert the extender into position 4 on the pedestal (see Figure 14). Figure 13. Extending the Pedestals for Two Cabinets Figure 14. Extending the Pedestals for Three or More Cabinets Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 41 (see Figure 15). Adjust the pedestals to the size of the UPS and secure the pedestals with the captive screws. Figure 15. Tower Position with Two Cabinets Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 42 Figure 16. Installing the Joining Brackets 10. If installing additional EBMs, repeat Step 6 for each cabinet. 11. Continue to the following section, “Installing the UPS.” Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 43: Installing The Ups

    NOTE If there are five or more EBMs, do not connect the EBM communication cable. See “Configuring the UPS for EBMs” on page 50 to set the number of installed EBMs. Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 44 If you are installing a remote power-off (RPO) switch, see the following section, “RPO Installation,” to install the switch before powering on the UPS. Continue to “UPS Electrical Connections” on page 38. Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 45: Rpo Installation

    Installation of the RPO function must be carried out in compliance with applicable regulations. The cable is not included. In order to fully de-energize devices and the Avaya 9135 with the RPO port, it is necessary to: Use a two-position switch (normally-open or normally-closed contact and held more than one second).
  • Page 46: Ups Electrical Connections

    Required Cable Cross-Sections Function Wiring Terminal block cable capacity 6 mm , solid or stranded wire (maximum 8 mm or 10 AWG). Capacity for ground/earthing conductor Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 47: Connecting The Power Cables

    C A U T I O N Always connect the ground/earthing wire first. Insert the output cable through the output cable opening. Connect the three wires to the output terminal block. Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 48 NOTE If more than one load is connected to the UPS, the total capacity of the loads should not exceed 30A. Figure 22. Connecting the Power Cords Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 49: Ups Rear Panel

    EBM Battery Connector Network Management Card Relay Port USB Port RPO Port RS- -232 BATT. NO. RPO RS-232 Port EBM RJ-11 Connector Figure 23. 6000 VA Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 50 INSTALLATION Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 51: Operation

    Figure 24. UPS Control Panel NOTE The On/Off button controls only the UPS output. The On/Off button has no effect on equipment connected to the UPS. Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 52: Turning The Ups On

    To turn on the UPS without using utility power, press and hold the button for three seconds. The UPS starts up in Battery mode and supplies battery power to your equipment. Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 53: Turning The Ups Off

    For a full shutdown of UPS and connected load, the upstream circuit breaker (not included) should be set to the OFF position. Operating Modes The Avaya 9135 front panel indicates the UPS status through the UPS indicators. Figure 25 shows the UPS front panel indicators and controls. On Battery Indicator...
  • Page 54: Normal Mode

    End of backup time: all indicators turn off. The alarm beeps continuously and the UPS displays End of backup time Battery low. When utility power is restored after the UPS shuts down, the UPS automatically restarts. Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 55: Bypass Mode

    Local Settings Model Output Settings Alarm History ON/OFF Settings Manual Batt Test Battery Settings LED & Buzzer Test Statistics Figure 26. Menu Map for Display Functions Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 56: Access To Measurements

    French, German, Italian, Portuguese, Spanish Date / Time Format International US (MM-DD-YYYY/HH:MM AM/PM) (DD-MM-YYYY/HH :MM) Date / Time Change GMT + 1 MM-DD-YYYY/HH :MM adjustable (Continental Europe) Audible Alarm Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 57 Automatic shutdown on battery if output load level <10% Sleep Mode Enable Disable Remote Command Enable Disable Enables consideration of shutdown or restart orders from software to be authorized Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 58: Configuring The Ups For Ebms

    Use the button to select the Battery Settings menu and press the button. Use the button to select the User Batt Settings option and press button. Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 59: Running Battery Tests

    195V during a battery test, the UPS returns to Normal mode. A new test cannot be started until the battery voltage returns to greater than 195V. Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 60: Access To Maintenance

    No / Yes Life Cycle Monitoring Enable / Disable Life cycling monitoring alarms Statistics Auto Statistics Statistics Custom Statistics Reset Date ? Are you sure ? Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 61: Life Cycle Monitoring

    Table 8. LCM Warning Details LCM Warning Details Signification BATTERY CHECK RECOMMENDED Battery is approaching its reliability end of life. Risk to reduce dramatically backup time. Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 62: Reset Or Disable Lcm

    To disable all LCM messages, select disable all while in the LCM menu. Be careful: if you disable all LCM messages, you will not be aware of any LCM events that can happen on the UPS. Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 63: Additional Ups Features

    The USB port is hot-pluggable. Connect the USB cable to the USB port on the UPS rear panel (see Figure 30). Connect the other end of the USB cable to the USB port on your computer. Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 64: Relay Port

    Output relays specifications: Voltage: 48 Vdc maximum Current: 2A maximum Power: 62.5 VA, 30W Example: for 48 Vdc, Imax=625 mA Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 65 Remote power-off (RPO) signal (5–27 Vdc, 10 mA max) Operation on mains (not on battery) User common Operation on automatic bypass Low Battery Load protected Operation on battery Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 66 ADDITIONAL UPS FEATURES Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 67: Maintenance

    Replace the faulty power module with one of the same power rating (6000 VA) and secure with the power module brackets. Replace the UPS front cover. Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 68: Hot-Swapping The Battery Tray

    Replace the battery tray and secure with the battery retaining brackets. NOTE To ensure safety and high performance, use only batteries supplied by Avaya. Replace the UPS front cover. Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual...
  • Page 69: Specifications

    70.5 kg (155.4 lb) × × (17.5” 5.1” 25.6”) Table 12. Power Connections Model Input Connection Output Receptacles 6000 VA 10 ft, L6-30P power cord (4) NEMA L6-30R Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 70 4 min 17 min 33 min 50 min 1 hr 7 min NOTE Battery times are approximate and vary depending on the load configuration and battery charge. Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 71: Troubleshooting

    NOTE In case of ”LCM WARNING”, see “Life Cycle Monitoring” on page 53. Escape Down Enter Figure 34. Troubleshooting LED Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 72: Troubleshooting Not Requiring Avaya Service

    INVERT LIMITATION Short circuit conditions on output devices. Check the installation at the UPS output (wiring, fault equipment). Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 73: Troubleshooting Requiring Avaya Service

    Use ”Enter” button to display details. (see page 60). FRAME FAULT Internal chassis fault detected. Use ”Enter” Call the Help Desk. button to display details. Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 74: Obtaining Service

    Customer return address and contact information Parts List SAP Code Description 700465446 6000 VA, 120V UPS Module, Avaya 9135 700465495 Extended Battery Module for the 6000 VA Avaya 9135 Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual 164201769 Rev 1...
  • Page 76 340-08710 AA *1642017691* 164201769 1...