Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual www.avayaups.com...
Page 3
Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual www.avayaups.com...
Page 4
Avaya and the Avaya logo are trademarks of Avaya Inc. and may be registered in certain jurisdictions. ConnectUPS is a trademark of Powerware Corporation. ECopyright 2004 Avaya Inc. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Avaya Inc.
Extended Battery Cabinet (EBC A through F) for applications that require more than one hour of run time. Up to two EBCs can be connected to the UPS. Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual 164201543 Rev A...
A maximum of seven power and/or battery charger modules can be installed in the system. Battery modules used in the Avaya RS9 system weigh 30 lb (14 kg). Use care in lifting and moving battery modules. Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual...
A 9-slot External Battery Module Cabinet is also available. Front Panel Display Front Cover Panels Cabinet Base Figure 1. Nine-Slot Cabinet (Front View) Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual 164201543 Rev A...
Page 10
Introduction Communication Slots Entrance Panel Figure 2. 9-Slot Cabinet (Rear View) Handle/Latch Handle Release Thumbscrew Insertion/Extraction Cams Figure 3. Power Module (700248974) Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual 164201543 Rev A...
NOTE Do not block the ventilation holes on each side and the back of the unit. Location Requirements Install the Avaya RS9 UPS as close as possible to the equipment or the load distribution panel it will protect. If this distance is more than 25 ft (7.6m), transient noise can reappear in the electrical distribution...
Installation Setup UPS Setup The Avaya RS9 UPS is shipped in a carton on a shipping pallet. Power and battery modules are shipped in separate boxes on another pallet. NOTE Do not attempt to lift the cabinet by the module shelves or other convenient edges or panels.
Installation Setup Moving the Cabinets The Avaya RS9 UPS and EBMC are very heavy with power and battery modules installed. Before moving the cabinets, remove the power and battery modules. Move the modules separately from the cabinets. C A U T I O N Do NOT attempt to raise the cabinet with the power or battery modules installed.
Page 16
Installation Setup Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual 164201543 Rev A...
To accommodate the feature of easy system expandability, it is recommended that NOTE initial installation of the Avaya RS9 UPS contain wiring to support a 18 kVA unit. See Table 2 for recommended conductor size to wire the input circuit breaker.
Risk of electrical shock. C A U T I O N To prevent electrical shock or damage to the equipment, verify that the Avaya RS9 UPS is OFF before you remove the entrance panel. The circuit breaker or disconnect switch must also be off at the AC input service panel.
Page 20
4. Torque the screws holding all input and output power conductors to the values specified in Table 2 on page 12. Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual 164201543 Rev A...
Page 21
120/120 for 240, 120/120 for 208, or 127/127 for 220 Vac, as selected through the front panel display. (3-Wire Plus Ground Input) (2 PEN) 100/200, 110/220, 120/208, 120/240, 127/220 Vac Figure 9. UPS Input Wiring Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual 164201543 Rev A...
Page 22
Parameter 4-2-4 set to 200, 220, 208, or 240, as required. N/-DC 200, 220 100, 110, 127, or 120 208, or 240 100, 110, 127, or 120 Figure 10. Split-Phase Output Connections Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual 164201543 Rev A...
Page 23
3, item 2 to view or change the EPO switch type.) 11. When all connections have been made and checked, reinstall the UPS cabinet rear panels using the original screws. Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual 164201543 Rev A...
2. Locate the 3-slot section in the UPS cabinet that contains the power entrance panel. Unscrew and remove the rear panel of this section (see Figure 13). Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual 164201543 Rev A...
Page 26
Replace the clamp with a panel-to-conduit feedthrough and secure it with the star nut. Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual 164201543 Rev A...
Page 27
UPS power entrance panel and the battery cabinet entrance panel as shown in Figure 15. – Figure 15. Battery Cable Installed in Battery Cabinet Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual 164201543 Rev A...
Page 28
Figure 15. Torque all three compression lugs to 75–85 in lb (8.5–9.6 Nm). 10. Reinstall the rear panel using the original screws. 11. Continue to “UPS Startup” on page 23. Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual 164201543 Rev A...
UPS is not connected to an AC supply. When AC input voltage is present, the Avaya RS9 system can provide output voltage even though its batteries are disconnected. To confirm that there is no UPS output voltage, always disconnect all of the AC input sources and unplug all battery strings and optional Extended Battery Cabinets.
Raise the module handle to secure the module into the cabinet. Be sure the handle latch snaps into place. Tighten the thumbscrew on the handle. Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual 164201543 Rev A...
A through F), check the cord connections between the UPS and the battery cabinet. 3. Ensure that all power modules are properly installed and latched into the UPS cabinet. Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual 164201543 Rev A...
Page 32
(See “DB-9 Communication Port” on page 44 for details.) 9. Turn on the equipment that is connected to the UPS. Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual 164201543 Rev A...
When the displayed value is correct, press the button. Set Time time 14:51:38 <- -> Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual 164201543 Rev A...
Page 34
EBC C EBC D EBC E EBC F (2) EBC D (2) EBC E (2) EBC F 1040 External Capacity extamphr 0028.8 <- -> Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual 164201543 Rev A...
Page 35
8. The UPS is now ready to operate, and displays the normal On/Off function screen. These configuration parameters are accessible during normal UPS operation by pressing the Config button through the front panel display. Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual 164201543 Rev A...
Page 36
UPS Startup Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual 164201543 Rev A...
Electromagnetic interference (EMI) and surge circuitry still protect the loads from voltage spikes and noise. Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual 164201543 Rev A...
If the UPS has been turned off, press the ON button through the front panel display to turn the UPS on again. Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual 164201543 Rev A...
Off to Battery. Removing Input Power Always put the Avaya RS9 UPS into the Off mode before removing input power. Avaya RS9 system batteries will discharge if the input line voltage is disconnected or turned off without first turning off the Avaya RS9 UPS.
(numbered from the top down) for a specific power module’s parameters. #0 is defined as System, enabling you to observe overall system operation. Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual 164201543 Rev A...
Page 41
External Battery Module Cabinet or Extended Battery Cabinets.) Md: AUTO M4-B7-12 St: ON LINE acvout 232 V Config Menu Figure 22. Front Panel Display (Normal Operation) Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual 164201543 Rev A...
Use the Menu map (Figure 26 on page 40) to find the parameter you need to change, and move through the menu structure until the parameter name appears on the display. Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual 164201543 Rev A...
Reading the Avaya RS9 System Logs The Avaya RS9 system makes an entry in its logs each time it sounds an alarm or runs on battery power. This information can help in diagnosing power problems. You can display the UPS Inverter and Alarm logs on the unit’s front panel display;...
Figure 25. Alarm Entry for Specific Slot Number Menu Map Figure 26 is an illustration of how to access all Avaya RS9 system parameters. The menu structure has 6 primary-level menus, named System Status Menu (1) through Service Menu (6). Under each primary menu are secondary items, each numbered by its location under the primary menu.
Page 46
(ESC) 5 3 Model Name 5 4 Serial Number 5 5 Software Version 6 Service Menu (Top) Figure 26. Avaya RS9 System Menu Map Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual 164201543 Rev A...
It also gives you a complete record of critical power events, and it notifies you of important UPS or power information. If there is a power outage and the Avaya RS9 system battery power becomes low, LanSafe software can automatically shut down your computer system to protect your data before the UPS shutdown occurs.
Web/SNMP card or other similar communication interfaces. These interface cards extend the capabilities of the Avaya RS9 system to provide compatibility with network and remote monitoring/management systems. Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual 164201543 Rev A...
Service Menu. See Figure 7 on page 14 and Figure 11 on page 17 to make the connection for all dedicated input signals. Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual 164201543 Rev A...
When the AC Failure condition no longer exists, the signal returns to the RS-232 Low state (positive voltage). DC Supply Voltage Nominal 12 Vdc/5W; 8V minimum, 24V maximum. (Default) Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual 164201543 Rev A...
Menu (menu 1) online and on battery. S Check the MOV surge suppression pack. For more information on preventive maintenance checks, contact your Avaya service representative. Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual 164201543 Rev A...
NOTE The Avaya RS9 UPS will operate with uncharged (or no) batteries, but will have limited (or no) battery backup capability. Backup protection requires at least three internal battery strings (two battery modules installed side-by-side equals one string) unless an Extended Battery Cabinet is used.
Label the original module with masking tape or some other identifier. Update the customer record to reflect the replacement parts. Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual 164201543 Rev A...
Page 54
6. Raise the module handle to secure the module into the cabinet. Be sure the handle latch snaps into place. Tighten the thumbscrew on the handle. 7. Reinstall the front cover panel. Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual 164201543 Rev A...
Each power module weighs 17 lb (8 kg) Each battery module weighs 30 lb (14 kg) Each battery charger module weighs 17 lb (8 kg) Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual 164201543 Rev A...
Page 56
For redundant power module operation (N+X), increase the input current rating by 2A for each additional redundant power module. **To accommodate the feature of easy system expandability, it is recommended that initial installation of the Avaya RS9 UPS contain wiring to support the maximum capacity of the UPS cabinet. If you are installing a battery charger module, refer to the input circuit breaker requirements in Table 1 on page 12.
Page 57
For redundant power module operation (N+X), increase the input current rating by 2A for each additional redundant power module. **To accommodate the feature of easy system expandability, it is recommended that initial installation of the Avaya RS9 UPS contain wiring to support the maximum capacity of the UPS cabinet. If you are installing a battery charger module, refer to the input circuit breaker requirements in Table 1 on page 12.
Page 58
The air around the UPS must be clean and free of dust, corrosive chemicals, and other contaminants. The Avaya RS9 UPS uses internal fans to circulate the air for cooling. The air must be free to circulate around the UPS and battery cabinet(s). Do not operate the UPS in a sealed room or container.
Press the button to scroll down through the log to view older alarms. Install the LanSafe software? See the instructions accompanying the LanSafe software CD. Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual 164201543 Rev A...
(A) silences the audible alarm, button (B) clears the alarm display, and button (C) performs the normal Escape function to exit from the alarm display. The button enables you to scroll through all alarms. Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual 164201543 Rev A...
Page 61
S the red LED next to the front panel display illuminates S sounds an audible alarm S displays an alarm message Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual 164201543 Rev A...
Page 62
The UPS has shut down due to Remove excess load(s) from the UPS output and restart excessive load. the UPS by pressing the ON button through the front panel display. Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual 164201543 Rev A...
Page 63
Contact your Avaya service Incompatible Module system. representative. 5 Fan Failure The UPS has detected a module fan Contact your Avaya service representative. problem that requires service. Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual 164201543 Rev A...
Page 64
Insufficient Modules redundancy level while protecting the load. The UPS will protect the load, but will not be fault tolerant. Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual 164201543 Rev A...