Avaya 9130 1000–3000 VA Uninterruptible Power Systems Site Preparation, Installation and Operator’s Manual www.powerware.com/avaya...
Page 3
Avaya 9130 1000–3000 VA Uninterruptible Power Systems Site Preparation, Installation and Operator’s Manual www.powerware.com/avaya...
Page 4
Association, Inc. Phillips is a registered trademark of Phillips Screw Company. All other trademarks are property of their respective companies. ECopyright 2008 Avaya Inc. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Avaya.
Page 5
Class B EMC Statements (Low Voltage Models up to 1500 VA and High Voltage Models up to 3000 VA) FCC Part 15 This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to NOTE part 15 of the FCC Rules.
Page 6
Requesting a Declaration of Conformity Units that are labeled with a CE mark comply with the following harmonized standards and EU directives: Harmonized Standards: IEC 61000-3-12 EU Directives: 73/23/EEC, Council Directive on equipment designed for use within certain voltage limits 93/68/EEC, Amending Directive 73/23/EEC 89/336/EEC, Council Directive relating to electromagnetic compatibility 92/31/EEC, Amending Directive 89/336/EEC relating to EMC...
— causing hours of lost productivity and expensive repairs. With the Avaya 9130, you can safely eliminate the effects of power disturbances and guard the integrity of your equipment. Providing outstanding performance and reliability, the Avaya 9130’s unique...
Page 10
INTRODUCTION Figure 1 shows the Avaya 9130 UPS, and Figure 2 shows the optional EBM. Figure 1. The Avaya 9130 UPS Figure 2. The Avaya 9130 EBM Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
If the UPS requires any type of transportation, verify that the UPS is unplugged and turned off and then disconnect the UPS internal battery connector (see Figure 20 on page 62). Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Page 12
I overensstemmelse med internationale normer og bestemmelser for el-installation må det udstyr, der er forbundet til udgangen af denne UPS, tilsammen ikke overskride en jordafdelingsspænding på mere end 3,5 milliampere. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Sluit om brandgevaar te voorkomen de apparatuur uitsluitend aan op een circuit voorzien van een overstroombeveiliging voor vertakte circuits van maximaal 100 A in overeenstemming met de NEC (Nationale Elektriciteitsvoorschriften), ANSI/NFPA 70. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Page 14
Ympäristön lämpötila ei saa ylittää 40 °C. Älä käytä lähellä vettä ja vältä kosteita tiloja (95 % maksimi). Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Page 15
La température ambiante ne doit pas dépasser 40 °C. Ne pas utiliser à proximité d’eau ou dans une atmosphère excessivement humide (95 % maximum). Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Page 16
W A R N U N G Die USV führt lebensgefährliche Spannungen. Alle Reparatur- und Wartungsarbeiten sollten nur von Kundendienstfachleuten durchgeführt werden. Die USV enthält keine vom Benutzer zu wartenden Komponenten. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Page 17
Il presente manuale contiene importanti istruzioni da seguire durante l’installazione e la manutenzione dell’UPS e delle batterie. Leggere integralmente le istruzioni prima di utilizzare l’apparecchiatura e conservare il presente manuale per futuro riferimento. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Page 18
Le batterie devono essere smaltite in modo corretto. Per i requisiti di smaltimento fare riferimento alle disposizioni locali. Non gettare mai le batterie nel fuoco poichè potrebbero esplodere se esposte alle fiamme. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Page 19
Batterier må fjernes på korrekt måte. Se lokale forskrifter vedrørende krav om fjerning av batterier. Kast aldri batterier i flammer, da de kan eksplodere, hvis de utsettes for åpen ild. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Page 20
Siga as instruções apropriadas ao desfazer-se das baterias. Consulte os códigos do local para maiores informações sobre os regulamentos de descarte de produtos. Nunca jogue as baterias no fogo, porque há risco de explosão. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Page 21
Для обеспечения соблюдения требований международных стандартов и требований к разводке электрических цепей, суммарная величина тока утечки на землю всего оборудования, подключенного к выходу ИБП, не должна превышать 3,5 миллиампера. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Para reducir el riesgo de incendio, realice la conexión únicamente hacia un circuito que cuente con un máximo de 100 amperios de protección contra sobrecorriente de circuito derivado, de acuerdo con el Código Eléctrico Nacional, ANSI/NFPA 70. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Page 23
är kontrollerade och där inga ledande föroreningar förekommer. Omgivande temperatur får ej överstiga 40°C. Använd inte utrustningen nära vatten eller vid hög luftfuktighet (max 95 %). Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Page 24
Håll ej behörig personal borta från batterierna. Batterierna måste avyttras enligt anvisningarna i lokal lagstiftning. Använda batterier får aldrig brännas upp. De kan explodera. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
NOTE Check the battery recharge date on the shipping carton label. If the date has passed and the batteries were never recharged, do not use the UPS. Contact your Avaya service representative. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual...
NOTE Discard the EBM user’s guide if you are installing the EBM with a new UPS at the same time. Use the UPS user’s guide to install both the UPS and the EBM. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
INSTALLATION Installation The Avaya 9130 rackmount cabinet comes with all of the hardware required for installation in a standard EIA or JIS seismic rackmount configuration with square and round mounting holes. The rail assemblies adjust to mount in 48-cm (19-inch) racks with front to rear rail distances from 61 to 76 cm (24 to 30 inches) deep.
Adjust each rail size for the depth of your rack. Rear Rails × 8 Pan-Head Screws (6 places) Left Rail Right Rail Figure 3. Assembling the Rails Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Page 29
Align the mounting brackets with the screw holes on each side of × the UPS and secure with the supplied M4 8 flat-head screws (see Figure 5). Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Page 30
Repeat for any optional cabinets. M6 Cage Nuts (4 places) × 16 Pan-Head Screws (4 places) Figure 6. Securing the Front of the Cabinet Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
To remove the cover, remove and retain the two screws on the right side of the cover. Grasp the top and bottom of the cover and slide the cover to the right. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Page 32
Clip the wires of the rightmost connector to the battery panel in its new position. 3000 VA models. Connect red to red, and black to black. Press the two parts tightly together to ensure a proper connection. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Page 33
“Remote Emergency Power-off” (REPO) on page 53 to install the REPO switch before powering on the UPS. Continue to “UPS Initial Startup” on page 29. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
To remove the cover, remove and retain the two screws on the right side of the cover. Grasp the sides of the cover and slide the cover to the left and then away from the cabinet. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Page 35
EBM cable knockout on the top and bottom of the EBM front cover. See Figure 11 for the location of the EBM cable knockouts. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Page 36
Verify that the EBM connections are tight and that adequate bend radius and strain relief exist for each cable. 1000/1500 VA Models 3000 VA Models Figure 12. Typical EBM Installation Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Verify that the UPS transfers to Standby mode (”UPS on standby”). Press the button on the UPS front panel for at least one second. The UPS front panel display changes status to “UPS starting...” Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Page 38
14. If you installed an optional REPO, test the REPO function: Activate the external REPO switch. Verify the status change on the UPS display. Deactivate the external REPO switch and restart the UPS. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Page 39
INSTALLATION NOTE The internal batteries charge to 90% capacity in less than 3 hours. However, Avaya recommends that the batteries charge for 48 hours after installation or long-term storage. If optional EBMs are installed, see the recharge times listed in Table 19 on page 75.
Page 40
INSTALLATION Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Chapter 4 Operation This chapter contains information on how to use the Avaya 9130, including front panel operation, operating modes, UPS startup and shutdown, transferring the UPS between modes, retrieving the Event Log, setting the power strategy, and configuring bypass settings, load segments, and battery settings.
( and ) to scroll through the menu structure. Press the Enter ) button to select an option. Press the button to cancel or return to the previous menu. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Page 43
UPS Type / Part Number / Serial Number / Firmware Settings User Settings See Table 3 for details. Service Settings For administrative purposes only. This menu is password-protected. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
120V (low voltage models) [200V] [208V] [220V] [230V] [240V] 230V (high voltage models) [Autosensing] Output Frequency [50Hz] [60Hz] [Autosensing] Autosensing * See “Configuring Bypass Settings” on page 44. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Page 45
UPSs with separate supply sources for the rectifier and bypass inputs. On Battery Notice Delay [0] [1s] [2s] . . . [99s] * See “Configuring Bypass Settings” on page 44. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Page 46
[Enabled] [Disabled] Enabled Predictive Maintenance Notices [Enabled] [Disabled] Enabled Remote Emergency Power-off (REPO) [Open] [Closed] Open Input Polarity * See “Configuring Bypass Settings” on page 44. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
OPERATION Operating Modes The Avaya 9130 front panel indicates the UPS status through the UPS indicators (see Figure 13 on page 33). Normal Mode During Normal mode, the indicator illuminates solid and the UPS is powered from the utility. The UPS monitors and charges the batteries as needed and provides filtered power protection to your equipment.
10 seconds. If the UPS is waiting on commands and utility fails, unit and logic power turn off in approximately 30 seconds. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
UPS is operating normally and any loads are powered. The UPS should be in Normal mode. Press the button until the start screen appears. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
NOTE Releasing the button before three seconds returns the UPS to its original operating mode. Switch off utility power where the UPS is connected. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
To set the power strategy: Press any button to activate the menu options, then select SETTINGS, USER SETTINGS, and POWER STRATEGY. Select HIGH EFFICIENCY or NORMAL, and ENTER to confirm. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Unsynchronized Transfers. The default allows an unsynchronized transfer to Bypass. You can configure the setting to not allow such transfers. This setting can be overruled by the “Qualify Bypass” setting. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Set the shutdown delay for one load segment, and ENTER to confirm. Set the other load segment if applicable. NOTE Load segment On/Off commands issued through the Control menu overrule the user settings for load segments. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
NOTE The UPS contains one battery string; each EBM contains two battery strings. Press the button to save the setting. Press the button until the start screen appears. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
If the battery voltage drops below the threshold, the UPS returns to Normal mode and the front panel displays “Battery Test Failed.” Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
“Automatic Start Delay” setting. You can also configure UPS restart to depend on the battery charge level, using the “Battery Charge % to Restart” setting. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
See “Rear Panels” on page 76 for rear panel diagrams for each model. ConnectUPS-BD Web/SNMP Card REPO Output Input RS-232 Standard Relay Output Contact Figure 14. Communication Options and Control Terminals (1000 VA, 120V Model Shown) Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
To establish communication between the UPS and a computer, connect your computer to one of the UPS communication ports using an appropriate communication cable (not supplied). See Figure 14 for the communication port locations. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Page 59
When the selected condition is active, output signals on Pins 1 and 8 shift from Low (positive voltage) to High (negative voltage). When the condition no longer exists, the output signal returns to Low. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
10 Mb Network LED (yellow) Status LED (yellow) 100 Mb Network LED (green) Reset Switch DIP Switch NETWORK Ethernet Connector COM Port Figure 16. ConnectUPS-BD Panel Details Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
(12–22 AWG) 0.82 mm (18 AWG) NOTE Leave the REPO connector installed in the REPO port on the UPS even if the REPO function is not needed. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
An additional four relay outputs can be obtained with the compatible Relay Interface Card. Configure the relay outputs with the “Relay Configuration” setting in “User Settings” on page 36. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
REPO terminal input. See Figure 14 on page 49 for the locations of the ports. Configure the inputs with the “Signal Inputs” setting in “User Settings” on page 36. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Page 64
If active, the UPS generates the “Building Alarm 1” alarm. Table 7. Polarity Options Input Description High Active state on high voltage (+Udc) level Active state on low voltage (GND or -Udc) level Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
It also gives you a complete record of critical power events, and it notifies you of important UPS or power information. If there is a power outage and the Avaya 9130 UPS battery power becomes low, Powerware LanSafe software can automatically shut down your computer system to protect your data before the UPS shutdown occurs.
Page 66
COMMUNICATION Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Check the battery recharge date on the shipping carton label. If the date has passed and the batteries were never recharged, do not use the UPS. Contact your Avaya service representative. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Never dispose of batteries in a fire. Batteries may explode when exposed to flame. Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes and may be extremely toxic. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
NOTE A ribbon cable connects the LCD control panel to the UPS. Do not pull on the cable or disconnect it. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Page 70
Grasp an edge of the battery cover plate and pull it forward gently. Remove and retain the battery cover plate. See Figure 20 for the location of the battery cover plate. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Page 71
Reinstall the two screws on the right side of the right front cover. 11. Continue to “Testing New Batteries” on page 66. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Top EBM Cable Knockout EBM Cover Hook Bottom EBM Cable Knockout (underneath cover) Figure 21. Removing the EBM Front Cover Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Page 73
EBM. Repeat for any additional EBMs. Verify that the EBM connections are tight and that adequate bend radius and strain relief exist for each cable. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
During the battery test, the UPS transfers to Battery mode and discharges the batteries for 25 seconds. The front panel displays “Battery test running” and the percentage of the test completed. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
To keep the UPS firmware updated with the latest improvements and benefits, visit www.powerware.com/avaya often for updates. You can download the latest firmware version and the instructions for installing it. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Page 76
UPS MAINTENANCE Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Table 9. Extended Battery Module Model List EBM Model Battery Voltage For Power Ratings 1000 VA 36 Vdc 1000 VA 1500 VA 48 Vdc 1500 VA 3000 VA 72 Vdc 3000 VA Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Page 78
50/60 Hz auto-sensing Frequency Range 40–70 Hz before transfer to battery Bypass Voltage Range +10/-15% of nominal (default) Noise Filtering MOVs for normal and common mode noise Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Page 79
IEC C14-10A Schuko 10A to IEC 320-10A 1500 VA, 208/230/240V IEC C14-10A Schuko 10A to IEC 320-10A 3000 VA, 208/230/240V IEC C20-16A Schuko 16A to IEC 320-16A Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Page 80
Transfer Time Online mode: 0 ms (no break) High Efficiency mode: 10 ms maximum (due to loss of utility) Power Factor Load Crest Factor 3 to 1 Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Page 81
(2) IEC-IEC 10A, (1) IEC 320-10A to Schuko 3-strip 3000 VA, 208/230/240V (8) IEC 320-10A, (1) IEC 320-16A (2) IEC-IEC 10A, (1) IEC 320-16A to Schuko 3-strip Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Page 82
Up to 3,000 meters (9,843 ft) above sea level Transit Altitude Up to 10,000 meters (32,808 ft) above sea level Audible Noise <50 dBA at 1 meter typical Leakage Current <1.5 mA Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Page 83
1 EBM: 9 hours; 2 EBMs: 15 hours; 3 EBMs: 21 hours; 4 EBMs: 27 hours Battery Port External three-pole Anderson connector on UPS for connection to EBM Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
For a description of communication features, see Figure 14 on page 49. Figure 22. 1000 VA, 120V Model Figure 23. 1000 VA, 208/230/240V Models Figure 24. 1500 VA, 120V Model Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Page 85
SPECIFICATIONS Figure 25. 1500 VA, 208/230/240V Models Figure 26. 3000 VA, 120V Model Figure 27. 3000 VA, 208/230/240V Models Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Page 86
SPECIFICATIONS Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Chapter 8 Troubleshooting The Avaya 9130 is designed for durable, automatic operation and also alerts you whenever potential operating problems may occur. Usually the alarms shown by the control panel do not mean that the output power is affected. Instead, they are preventive alarms intended to alert the user.
Page 88
The batteries are disconnected. Verify that all batteries are properly connected. If LED is on. the condition persists, contact your Avaya service representative. 1 beep every second. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Page 89
The UPS is in Standby mode. Supply power to the connected equipment: Press UPS output receptacles. the On/Off button for at least 1 second, until the front panel displays “UPS starting...”. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Page 90
Check that the “Serial Port Configuration” setting is work. speed is set incorrectly for USB. set to 9600 bps. See “User Settings” on page 36. USB requires 9600 bps. Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Extended Battery Module for the 1000 VA Avaya 9130 790341054090 Extended Battery Module for the 1500 VA Avaya 9130 790341054106 Extended Battery Module for the 3000 VA Avaya 9130 Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...
Page 92
TROUBLESHOOTING Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual 164201765 Rev 1...