Temperature
v Temperature: Select the temperature unit (°C or °F).
v High threshold: If this value is exceeded, a notification is sent if the
v Low threshold: If this value is exceeded, a notification is sent if the
v Hysteresis: Specify a value to prevent multiple notifications if the temperature
The high alarm is not displayed if the value drops below the high threshold -
hysteresis value.
The low alarm is not displayed if the value rises above the low threshold +
hysteresis value.
Humidity
v High threshold: If this value is exceeded, a notification is sent if the
v Low threshold: If this value is exceeded, a notification is sent if the
v Hysteresis: Specify a value to prevent multiple notifications if the humidity
The high alarm is not displayed if the value drops below the high threshold -
hysteresis value.
The low alarm is not displayed if the value rises above the low threshold +
hysteresis value.
External contacts
v Input #1 and Input #2: Enter an identifier that corresponds to the acquired
v when closed and when open: Enter names that are associated with the two
For the list of messages, see Table 39 on page 75.
66
Network Management Card : User's Guide
corresponding notification checkbox is selected on the Environment Settings
page. The default is 40°C (104°F).
corresponding notification checkbox is selected on the Environment Settings
page. The default is 5°C (41°F).
fluctuates around a threshold. The default is 2°C (36°F).
corresponding notification checkbox is selected on the Environment Settings
page. The default is 90%.
corresponding notification checkbox is selected on the Environment Settings
page. The default is 5%.
fluctuates around a threshold. The default is 5%.
contact (for example, rack door, air conditioning, or generator unit). The limit is
28 characters.
contact positions (for example, Open and Closed for a door and On and Off for a
generator).