Calibrate Page

The Calibrate page (FIG. 63) allows you to calibrate the touch panel for accurate button selection.
FIG. 63
Calibrate page
1.
Press and hold the center button on the navigation wheel for 6 seconds to access the Calibrate page (see
FIG. 53).
2.
Press the crosshairs in turn. If the crosshairs are not touched within ten seconds, the MVP-5200i will
return to the Protected Setup page.
3.
The page will read "Calibration Successful. Touch to continue." Touch anywhere on the screen to return
to the Protected Setup page.
If the screen is not touched at that point, the device will automatically return to the
Protected Setup page within 10 seconds.
Always calibrate the panel before its initial use, and after downloading new firmware.