Calibrate Page - AMX MVP-5100 Operation/Reference Manual

Hide thumbs Also See for MVP-5100:
Table of Contents

Advertisement

Protected Setup Pages

Calibrate Page

The Calibrate page (FIG. 56) allows you to calibrate the touch panel for accurate button selection.
FIG. 56
Calibrate page
1. Press and hold the reset button for 6 seconds to access the Calibrate page (see FIG. 44).
2. Press the crosshairs in turn. If the crosshairs are not touched within ten seconds, the MVP-5100 will
return to the Protected Setup page.
3. The page will read "Calibration Successful. Touch to continue." Touch anywhere on the screen to
return to the Protected Setup page.
If the screen is not touched at that point, the device will automatically return to the
Protected Setup page within 10 seconds.
Always calibrate the panel before its initial use, and after downloading new firmware.