Multi-Speed And Jog Frequency Settings - Hitachi SJ300 Series Instruction Manual

Hitachi instruction manual inverter sj300 series
Hide thumbs Also See for SJ300 Series:
Table of Contents

Advertisement

Multi-speed and
Jog Frequency
Settings
"A" Function
Func.
Name
Code
A019 Multi-speed operation
selection
A020 Multi-speed frequency
setting
A220 Multi-speed frequency
setting, 2nd motor
A320 Multi-speed frequency
setting, 3rd motor
A021
Multi-speed frequency
to
settings
A035
(for both motors)
A038 Jog frequency setting
A039 Jog stop mode
The SJ300 inverter has the capability to store and output up to 16 preset frequencies to the
motor (A020 to A035). As in traditional motion terminology, we call this multi-speed profile
capability. These preset frequencies are selected by means of digital inputs to the inverter. The
inverter applies the current acceleration or deceleration setting to change from the current
output frequency to the new one. The first multi-speed setting is duplicated for the second
motor settings (the remaining 15 multi-speeds apply only to the first motor).
The jog speed setting is used whenever the Jog command is active. The jog speed setting range
is arbitrarily limited to 10 Hz to provide safety during manual operation. The acceleration to the
jog frequency is instantaneous, but you can choose from six modes for the best method for
stopping the jog operation.
Description
Two options; select codes:
00 Binary; up to 16-stage
speed using 4 intelligent
terminals
01 Single-bit; up to 8-stage
speed using 7 intelligent
terminals
Defines the first speed of a
multi-speed profile, range is
0 to 360 Hz
A020 = Speed 0 (1st motor)
Defines the first speed of a
multi-speed profile for 2nd
motor, range is 0 to 360 Hz
A220 = Speed 0 (2nd motor)
Defines the first speed of a
multi-speed profile for 3rd
motor, range is 0 to 360 Hz
A320 = Speed 0 (3rd motor)
Defines 15 more speeds,
range is 0 to 360 Hz.
A021 = Speed 1...
A035 = Speed 15
Defines limited speed for
jog, range is 0.5 to 9.99 Hz
Define how end of jog stops
the motor; six options:
00 Free-run stop, jogging
disabled during motor
run
01 Controlled deceleration,
jogging disabled during
motor run
02 DC braking to stop,
jogging disabled during
motor run
03 Free-run stop, jogging
always enabled
04 Controlled deceleration,
jogging always enabled
05 DC braking to stop,
jogging always enabled
Defaults
Run
Mode
Edit
–FE
–FU
–FR
Lo Hi
(EU)
(US)
(JP)
✘ ✘
00
00
00
✔ ✔
0.00
0.00
0.00
✔ ✔
0.00
0.00
0.00
✔ ✔
0.00
0.00
0.00
✔ ✔
0.00
0.00
0.00
✔ ✔
1.00
1.00
1.00
✘ ✔
00
00
00
3–13
SJ300 Inverter
Units
SRW Display
>A019 SPEED
SELECT
BINARY
Hz
>A020 SPEED
FS
0000.00Hz
Hz
>A220 SPEED
2FS
0000.00Hz
Hz
>A320 SPEED
3FS
0000.00Hz
Hz
>A021 SPEED
01S
0000.00Hz
Hz
>A038 Jogging
F
01.00Hz
>A039 Jogging
Mode
FRS

Advertisement

Table of Contents
loading

Table of Contents