Torque Limit

The Torque Limit function limits the motor output torque for sensorless vector control, sensor-
less vector control 0Hz domain, or vector control with feedback.
In the torque limit function, the following operational modes are available (selected by B040):
1. Four-quadrant individual setting mode – This mode sets torque limit in 4 zones, forward
2. Terminal selection mode – By use of torque limit select intelligent input terminals 1 and 2,
3. Analog input mode – This mode sets torque limit value by the voltage applied to terminal
4. Expansion Cards 1 and 2 – This function is valid when using the expansion card (SJ-DG).
When the torque limit enable function [TL] is assigned to an intelligent input terminal, torque
limiting occurs only when [TL] is ON. When the [TL] input is OFF, the inverter always uses the
default torque control limit of 200% maximum. That torque limit value corresponds to 200% of
the maximum inverter output current. Therefore, the output torque also depends on the particu-
lar motor in use. When the over-torque output [OTQ] is assigned in the intelligent output selec-
tion, it turns ON when the inverter is performing torque limiting.
Note 1: Unavailable for A344
Note 2: Unavailable for A244 and A344
driving and regenerating, reverse driving and regenerating. Limits for each quadrant are set
with B041 – B044 individually.
this mode changes and uses torque limits 1 – 4 set in B041 – B044. Selected torque limit
range is valid in all four quadrants.
[O2] (referenced to [L] for ground. An input of 0 – 10V corresponds to the torque limit
value of 0 to 200%. The selected torque limit value is valid in all four quadrants (whether
forward or reverse move, driving or regenerating).
Please refer to the SJ-DG instruction manual.
Code
Function
A044 /
Control method
A244
selection
B040
Torque limit
selection
B041
Torque limit 1
B042
Torque limit 2
B043
Torque limit 3
B044
Torque limit 4
C001
Intelligent input
to
terminal [1] to [8]
C008
function
C021
Intelligent output
to
terminal [11] to [15]
C025
function
Data or Range
00
V/f Constant torque
01
V/f Variable torque
02
V/f Free-setting torque *1
03
Sensorless vector *1
04
Sensorless vector, 0 Hz domain *1
05
Vector control with sensor *2
00
4-quadrant individual setting
01
Terminal selection
02
Analog [O2] input
03
Expansion card 1
04
Expansion card 2
0 to 200%
Forward-driving in 4-quadrant mode
0 to 200%
Reverse-regenerating in 4-quadrant
mode
0 to 200%
Reverse-driving in 4-quadrant mode
0 to 200%
Forward-regenerating in 4-quadrant
mode
40
Torque limit enable
41
Torque limit selection, bit 1 (LSB)
42
Torque limit selection, bit 2 (MSB)
10
In torque limit
4–37
SJ300 Inverter
Description