Hitachi SJ300 Series Instruction Manual page 144

Hitachi instruction manual inverter sj300 series
Hide thumbs Also See for SJ300 Series:
Table of Contents

Advertisement

4–6
Optional Controlled Decel and Alarm at Power Loss
The timing diagram below shows a power loss scenario and the related parameter settings.
During the controlled deceleration the inverter itself acts as a load to decelerate the motor. With
either a high-inertia load or a short deceleration time (or both), it is possible that the inverter
impedance will not be low enough to continue linear deceleration and avoid an over-voltage
condition on the DC bus. Use parameter B052 to specify a threshold for the over-voltage. In
this case, the inverter pauses deceleration (runs at constant speed). When the DC bus decays
again below the threshold, linear deceleration resumes. The pause/resume process will repeat as
necessary until the DC bus energy is depleted (under-voltage condition occurs).
DC bus (V)
B052
B051
Under-voltage
level
0
Output
Frequency
0
NOTE: (1) Be sure to set the over-voltage threshold greater than the DC bus voltage trigger
level (B052 > B051) for proper operation.
(2) Once the power loss deceleration function starts, it will complete and stop the motor even if
input power is restored. In that case, it automatically enables the Run mode again.
B054
B053
t
t

Advertisement

Table of Contents
loading

Table of Contents