Serial Network Parameter Settings - Hitachi SJ300 Series Instruction Manual

Hitachi instruction manual inverter sj300 series
Hide thumbs Also See for SJ300 Series:
Table of Contents

Advertisement

B–4
Introduction
Serial Network
Parameter
Settings
Several parameter settings are necessary to configure serial communications, listed below.
Function
Item
Code
C070
Data command source
C071
Baud rate
C072
Node address
C073
Data bits
C074
Parity
C075
Stop bits
C078
Wait time
For inverters on the same network, some settings must match from inverter to inverter. These
include:
• Baud rate
• Data bits
• Parity
• Stop bits
However, the node address on each inverter must be unique, used only once on the network.
Value
Description
02
Digital operator
03
RS485 connector
04
Expansion card #1
05
Expansion card #2
02
Loop-back test
03
2400 bps
04
4800 bps
05
9600 bps
06
19200 bps
1 to 32,
1 to 32 – Node or station address (unique
FF
to each inverter or device)
FF – Automatic broadcast (to all nodes on
transmit, allowed only on certain
commands (refer to each command
description in this appendix)
07
7 bits
08
8 bits
00
none
01
Even parity
02
Odd parity
01
1 bit
02
2 bits
0 to 1000 0 to 1000 ms time that the inverter waits
to respond to network master