Ul Cautions, Warnings, And Instructions; Sj300-004Lfu; Sj300-007Lfu; Sj300-015Lfu - Hitachi SJ300 Series Instruction Manual

Hitachi instruction manual inverter sj300 series
Hide thumbs Also See for SJ300 Series:
Table of Contents

Advertisement

xii
®
UL
Cautions, Warnings, and Instructions
Wiring Warnings
for Electrical
Practices and
Wire Sizes
Terminal Tighten-
ing Torque and
Wire Size
The Cautions, Warnings, and instructions in this section summarize the procedures necessary to
ensure an inverter installation complies with Underwriters Laboratories
WARNING: "Use 60/75°C Cu wire only" or equivalent.
WARNING: "Open Type Equipment." For models SJ300–750H to SJ300–1500H.
WARNING: "Suitable for use on a circuit capable of delivering not more than 100,000 rms
symmetrical amperes, 240 V maximum." For models with suffix L.
WARNING: "Suitable for use on a circuit capable of delivering not more than 100,000 rms
symmetrical amperes, 480 V maximum." For models with suffix H.
The wire size range and tightening torque for field wiring terminals are presented in the table
below.
Motor
Input
Output
Voltage
HP
kW
1/2
0.4

SJ300-004LFU

1
0.75

SJ300-007LFU

2
1.5

SJ300-015LFU

3
2.2

SJ300-022LFU

5
3.7

SJ300-037LFU

7.5
5.5
SJ300-055LFU
10
7.5
SJ300-075LFU
200V
15
11
SJ300-110LFU
20
15
SJ300-150LFU
25
18.5
SJ300-185LFU
30
22
SJ300-220LFU
40
30
SJ300-300LFU
50
37
SJ300-370LFU
60
45
SJ300-450LFU
75
55
SJ300-550LFU
200V
Wire Size Range (AWG)
Inverter Model
1/0 || 1/0 AWG
1/0 || 1/0 AWG
1/0 || 1/0 AWG
2/0 || 2/0 AWG
®
guidelines.
Torque
ft-lbs
20
1.1
18
1.1
14
1.1
14
1.1
10
1.1
8
1.8
6
1.8
4
3.6
2
3.6
1
3.6
1/0 AWG
6.5
6.5
6.5
10.1
10.1
(N-m)
1.5
1.5
1.5
1.5
1.5
2.5
2.5
4.9
4.9
4.9
8.8
8.8
8.8
13.7
13.7

Advertisement

Table of Contents
loading

Table of Contents