4–12
Using Intelligent Input Terminals
Wiring Diagram
Conventions
Forward Run/
Stop and Reverse
Run/Stop
Commands
The input wiring diagrams in this chapter are examples only. Default and non-default input
terminal assignments are noted throughout; your particular assignments may be different. The
wiring diagrams show the –xFU/–xFR model default [P24]–[PLC] jumper position (U.S./Jpn
versions), as shown below on the left. The common (return) for inputs is [CM1] in this case.
The diagram on the right shows the default jumper position and example input wiring for –xFE
models (Europe version). For this case, the common (return) for inputs is [P24]. Be sure the
jumper position and return terminal used match your application wiring needs.
–xFU/–xFR models (U.S./Jpn versions):
FW
RV
TH
FW
5
4
3
P24
PLC
CM1
Default jumper
position [P24]–[PLC]
and wiring example
(used throughout this
When you input the Run command via the dedicated terminal [FW], the inverter executes the
Forward Run command (high) or Stop command (low). When you input the Run command via
the programmable terminal [RV], the inverter executes the Reverse Run command (high) or
Stop command (low).
Opt.
Symbol
Function Name
Code
FW
Forward Run/Stop
01
RV
Reverse Run/Stop
C001, C002, C003, C004,
Valid for
C005, C006, C007, C008
inputs:
A002 = 01
Required
settings:
Notes:
• When the Forward Run and Reverse Run
commands are active at the same time, the
inverter enters the Stop Mode.
• When a terminal associated with either [FW]
or [RV] function is configured for normally
closed, the motor starts rotation when that
terminal is disconnected or otherwise has no
input voltage.
NOTE: The parameter F004, Keypad Run Key Routing, determines whether the single Run
key issues a Run FWD command or Run REV command. However, it has no effect on the [FW]
and [RV] input terminal operation.
WARNING: If the power is turned ON and the Run command is already active, the motor
starts rotation and is dangerous! Before turning power ON, confirm that the external Run
command is not active.
–xFE models (Europe version):
2
1
P24
chapter)
return
State
ON
Inverter is in Run Mode, motor runs
forward
OFF Inverter is in Stop Mode, motor stops
ON
Inverter is in Run Mode, motor runs
reverse
OFF Inverter is in Stop Mode, motor stops
Example: (Default input configuration
shown—see page 3–47. Jumper position
shown is for –xFU/-xFR models; for –xFE
models, see examples above.)
FW
RV
TH
FW
5
4
3
2
1
PLC
CM1
Default jumper
position [PLC]–[CM1]
and wiring example
return
Description
FW
RV
TH
FW
CM1
8
5
3
P24
PLC
CM1
7
6
4
2
See I/O specs on page 4–9.
1