Multi-Speed Select - Hitachi SJ300 Series Instruction Manual

Hitachi instruction manual inverter sj300 series
Hide thumbs Also See for SJ300 Series:
Table of Contents

Advertisement

Multi-Speed
The inverter can store up to 16 different fixed target frequencies (speeds) in parameters A020
to A035. Binary inputs select the speed through four of the intelligent terminals configured as
Select
binary-encoded inputs CF1 to CF4 per the table. These can be any of the eight inputs, and in
any order. You can use fewer inputs if you need eight or fewer speeds.
NOTE: When choosing a subset of speeds to use, always start at the top of the table, and with
the least-significant bit: CF1, CF2, etc.
The example with eight speeds in the figure below shows how input switches configured for
CF1 – CF3 functions can change the motor speed in real time.
Multi-speed Override Feature - The multi-speed function can selectively override the
external analog speed reference input. When the Frequency Source Setting parameter
A001=01, the control terminal inputs determine the output frequency. At the same time, the
inverter can use multi-speed select for output frequency if one or more intelligent inputs are
configured as a CF type (CF1 to CF4). When all CF input(s) are OFF, the control terminal input
determines the output frequency normally. When one or more CF input(s) are ON, then the
corresponding multi-speed setting (see the table above) overrides and becomes the output
frequency.
Input Function
Multi-
speed
CF4
CF3
Speed 0
0
0
Speed 1
0
0
Speed 2
0
0
Speed 3
0
0
Speed 4
0
1
Speed 5
0
1
Speed 6
0
1
Speed 7
0
1
Speed
3rd
7th
5th
2nd
1st
6th
4th
0th
Switches
CF1
CF2
CF3
Fwd Run
Multi-
speed
CF2
CF1
CF4
0
0
Speed 8
1
0
1
Speed 9
1
1
0
Speed 10
1
1
1
Speed 11
1
0
0
Speed 12
1
0
1
Speed 13
1
1
0
Speed 14
1
1
1
Speed 15
1
4–13
SJ300 Inverter
Input Function
CF3
CF2
CF1
0
0
0
0
0
1
0
1
0
0
1
1
1
0
0
1
0
1
1
1
0
1
1
1
t

Advertisement

Table of Contents
loading

Table of Contents