Hitachi SJ300 Series Instruction Manual page 116

Hitachi instruction manual inverter sj300 series
Hide thumbs Also See for SJ300 Series:
Table of Contents

Advertisement

3–48
"C" Group: Intelligent Terminal Functions
Func.
Name
Code
C011 Terminal [1] active state
C012 Terminal [2] active state
C013 Terminal [3] active state
C014 Terminal [4] active state
C015 Terminal [5] active state
C016 Terminal [6] active state
C017 Terminal [7] active state
C018 Terminal [8] active state
C019 Terminal [FW] active
state
The input logic convention is programmable for each of the six inputs. Most inputs default to
normally open (active high), but you can select normally closed (active low) in order to invert
the sense of the logic.
"C" Function
Description
Select logic convention,
two option codes:
00 normally open N.O.
01 normally closed N.C.
NOTE: An input terminal configured for option code 18 ([RS] Reset command) cannot be
configured for normally closed operation.
Defaults
Run
Mode
Edit
–FE
–FU
–FR
Lo Hi
(EU)
(US)
(JP)
✘ ✔
00
00
00
✘ ✔
00
00
00
✘ ✔
00
00
00
✘ ✔
00
00
00
✘ ✔
00
00
00
✘ ✔
00
01
00
✘ ✔
00
00
00
✘ ✔
00
00
00
✘ ✔
00
00
00
SRW Display
Units
>C011 IN-TM
O/C-1
NO
>C012 IN-TM
O/C-2
NO
>C013 IN-TM
O/C-3
NO
>C014 IN-TM
O/C-4
NO
>C015 IN-TM
O/C-5
NO
>C016 IN-TM
O/C-6
NO
>C017 IN-TM
O/C-7
NO
>C018 IN-TM
O/C-8
NO
>C019 IN-TM
O/C-FW
NO

Advertisement

Table of Contents
loading

Table of Contents