Analog Output Function Summary Table - Hitachi SJ300 Series Instruction Manual

Hitachi instruction manual inverter sj300 series
Hide thumbs Also See for SJ300 Series:
Table of Contents

Advertisement

3–56
"C" Group: Intelligent Terminal Functions
Option
Terminal
Code
Symbol
23
POK
24
FA4
25
FA5
26
OL2
Option
Function Name
Code
00
Output frequency
01
Output current
02
Output torque
03
Digital output
frequency
04
Output voltage
05
Input power
06
Electronic thermal
overload
07
LAD frequency
Output Function Summary Table
Function Name
Positioning completion ON
OFF
Frequency arrival type
ON
4 – over-frequency (2)
OFF
Frequency arrival type
ON
5 – at frequency (2)
OFF
Overload notice
ON
advance signal (2)
OFF
Analog Summary Table - The following table shows all eight functions available for assign-
ment to the three analog output terminals [FM], [AM], [AMI] at a glance. Detailed descrip-
tions, related parameters and settings, and example wiring diagrams are in
Operation" on page
4–62.

Analog Output Function Summary Table

Actual motor speed, represented by PWM
signal
Motor current (% of maximum rated output
current), represented by PWM signal
Rated output torque
Output frequency (available only at FM
output)
Rated output voltage to motor
Rated input power
Percentage of electronic overload attained
Internal ramp generator frequency
Description
when the load position is at the target
when the load position is not yet at the target
when output to motor is at or above the FA threshold
2 (C045) during accel
when the output to motor is below the FA threshold 2
(C046) during decel
when output to motor is at the FA threshold 2 (C045)
during accel, or at C046 during decel
when the output to motor is not at either the FA
threshold 2 (C045) during accel or at C046 during
decel
when output current is more than the set Threshold 2
for the overload signal (set with C111)
when output current is less than the set Threshold 2
for the overload signal
Description
"Analog Output
Corresponding Signal
Range
0 to max. frequency in Hz
0 to 200%
0 to 200%
0 to max. frequency in Hz
0 to 100%
0 to 200%
0 to 100%
0 to max. frequency in Hz

Advertisement

Table of Contents
loading