Run Signal

When the [RUN] signal is selected as an
intelligent output terminal, the inverter
outputs a signal on that terminal when it is
in Run Mode. The output logic is active
low, and is the open collector type (switch
to common).
Valid for
outputs:
Required
settings:
Notes:
• The inverter outputs the [RUN] signal
NOTE: The example circuit in the table above drives a relay coil. Note the use of a diode to
prevent the negative-going turn-off spike generated by the coil from damaging the inverter's
output transistor.
Opt.
Symbol
Function Name
Code
00
RUN
Run signal
11, 12, 13, 14, 15,
AL0 – AL2
(none)
whenever the inverter output exceeds the start
frequency specified by parameter B082. The
start frequency is the initial inverter output
frequency when it turns ON.
[FW, RV]
Motor
speed
start freq.
B82
Run
Signal
Output
Description
State
ON
when inverter is in Run Mode
OFF
when inverter is in Stop Mode
Example: (Default output configuration
shown—see page 3–53.)
Inverter output terminal circuit
14
15
+
RY
See I/O specs on page 4–9.
4–43
SJ300 Inverter
ON
t
RUN
13
11
CM2
12