The alarm output terminals operate as shown below (left) by default. The contact logic can be
inverted as shown (below right) by using the parameter setting C036. The relay contacts
normally open (N.O.) and normally closed (N.O.) convention uses "normal" to mean the
inverter has power and is in Run or Stop Mode. The relay contacts switch to the opposite
position when it is in Trip Mode or when input power is OFF.
Contact position after initialization
During normal running
When an alarm occurs or
power is turned OFF
AL1
AL0 AL2
Run
Contact
Power
State
N.C.
ON
Normal
(after
ON
Trip
initialize,
C036=01)
OFF
Contact position inverted by C036 setting
During normal running or
power is turned OFF
AL1
AL0 AL2
AL0 AL2
AL0-
AL0-
Contact
AL1
AL2
Closed
Open
N.O.
(set
Open
Closed
C036=00)
Open
Closed
SJ300 Inverter
When an alarm occurs
AL1
AL1
AL0 AL2
Run
AL0-
Power
State
AL1
ON
Normal
Open
ON
Trip
Closed
OFF
Open
4–49
AL0-
AL2
Closed
Open
Closed