Over-Torque Signal - Hitachi SJ300 Series Instruction Manual

Hitachi instruction manual inverter sj300 series
Hide thumbs Also See for SJ300 Series:
Table of Contents

Advertisement

4–50
Using Intelligent Output Terminals
Over-torque
Signal
The Over-torque function [OTQ] turns ON when the estimated value of output torque of motor
increases more than the arbitrary level set for the output. Recall that the torque limit function,
covered in
"Torque Limit" on page
conditions. Instead, the over-torque output feature only monitors the torque, turning ON output
[OTQ] if the torque is above programmable thresholds you set. The [OTQ] function is valid
only for sensorless vector control, 0-Hz domain sensorless vector control, or vector control
with sensor. Do not use the [OTQ] output, except for these inverter operational modes.
Code
C055
Over-torque, forward-driving level setting
C056
Over-torque, reverse-regenerating, level setting
C057
Over-torque, reverse-driving, level setting
C058
Over-torque, forward-regenerating, level setting
C021
Intelligent output terminal [11] to [15] function
to
C025
The assignment of the Over-torque function to an output terminal [OTQ] is detailed in the
following table.
Opt.
Symbol
Function Name
Code
07
OTQ
Over-torque
11, 12, 13, 14, 15,
Valid for
AL0 – AL2
outputs:
C055, C056, C057, C058
Required
A044 = 03 or 04 or 05
settings:
Notes:
• This output is valid only for sensorless
vector control, 0-Hz domain sensorless vector
control, or vector control with sensor
4–37, actually limits the torque during certain operating
Function/Description
Output
State
ON
when estimated torque exceeds the level
set in C055 to C058
OFF
when estimated torque is below the levels
set in C055 to C058
Example: (Default output configuration
shown—see page 3–53.)
Inverter output
terminal circuit
See I/O specs on page 4–9.
Data or Range
0 to 200%
0 to 200%
0 to 200%
0 to 200%
07
Description
OTQ
14
13
11
CM2
15
12
+
RY