Jumper Settings - Daikin FTXS09HVJU Service Manual

Inverter pair wall mounted type h-series
Hide thumbs Also See for FTXS09HVJU:
Table of Contents

Advertisement

Other Considerations
1.2

Jumper Settings

1.2.1 When 2 Units are Installed in 1 Room
When 2 indoor units are installed in 1 room, one of the 2 wireless remote controllers can be set for
different address.
How to set the different address
 Control PCB of the indoor unit
(1) Remove the shelter of the electrical box. (Refer to page 165 and 190 for removal procedure.)
(2) Cut the address jumper JA on the control PCB.
09/12 Class
 Wireless remote controller
(1) Slide the front cover and take it off.
(2) Cut the address jumper J4.
1.2.2 Jumper Setting
Other Considerations
Sheller
ADDRESS:
JA
JA
1
EXIST
ADDRESS
JB
CUT
2
JC
J4
Address
EXIST
1
CUT
2
Jumper
(On indoor control PCB)
JC
Power failure
recovery function
JB
Fan speed setting
when compressor is
OFF on thermostat.
(effective only at
cooling operation)
15/18/24 Class
Electric
parts box
PCB
(R0288)
J4
(R0291)
Function
When connected
(factory set)
Auto-restart
Fan speed setting ;
Remote controller
setting
SiUS04-904
(R2872)
When cut
Unit does not resume operation
after recovering from a power
failure. Timer ON-OFF settings
are cleared.
Fan rpm is set to "0"
<Fan stop>