Field Settings
Wireless Remote
(1) Remove the cover and take it off.
Controller
(2) Cut the address setting jumper.
ARC452 series
Caution
Replace the remote controller if you accidentally cut a wrong jumper.
Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of them.

5.2.4 Jumper Settings

CTXG, CTXS, FTXS, CDXS, FDXS, FVXS series
FVXS series only
For the location of the jumper, refer to the following pages.
218
Jumper
ADDRESS
EXIST
1
CUT
2
Jumper (on indoor
unit PCB)
JB
Fan speed setting
when compressor
stops for thermostat
OFF. (effective only
at cooling operation)
JC
Power failure
recovery function
Switch (on indoor unit
PCB)
SW2-4
Upward airflow limit
setting
CTXG09/12/18QVJUW(S): page 21
CTXS07LVJU, FTXS09/12LVJU: page 23
FTXS15/18/24LVJU: page 25
FDXS09/12LVJU, CDXS15/18/24LVJU: page 27
FVXS09/12/15/18NVJU: page 29
ARC466 series
Jumper
ADDRESS
EXIST
CUT
(R12065)
∗ Do not cut the left jumper.
Function
When connected
(factory set)
Fan speed setting;
Remote controller
setting
Auto-restart
Function
OFF
(factory setting)
Exposed or half
embedded
installation
SiUS121630EA
1
2
When cut
The fan stops.
The unit does not resume
operation after recovering from a
power failure. Timer settings are
cleared.
ON
Set the switch to ON position
when you install the indoor unit
embedded in the wall to avoid
condensation.
Trial Operation and Field Settings
(R18416)