Daikin FTXS09HVJU Service Manual page 131

Inverter pair wall mounted type h-series
Hide thumbs Also See for FTXS09HVJU:
Table of Contents

Advertisement

SiUS04-904
4.12.2 15/18/24 Class
F3
Remote
Controller
Display
The discharge pipe temperature control (stop, frequency dropping, etc.) is checked with the
Method of
temperature being detected by the discharge pipe thermistor.
Malfunction
Detection
 If a stop takes place 6 times successively due to abnormal discharge pipe temperature, the
Malfunction
Decision
 If the temperature being detected by the discharge pipe thermistor rises above 248°F (120°C),
Conditions
Stop temperatures (variable by models)
(1) 230°F (110°C): above 45Hz (rising), above 40Hz (dropping)
(2) 216°F (102°C): 30~45Hz (rising), 25~40Hz (dropping)
(3) 208°F (97.8°C) : below 30Hz (rising), below 25Hz (dropping)
 The error counter is reset if this or any other error does not occur during the following 60-minute
 Refrigerant shortage
Supposed
 Four way valve malfunctioning
Causes
 Discharge pipe thermistor defective
 Outdoor unit PCB defective
 Water mixed in the local piping
 Electronic expansion valve defective
 Stop valve defective
Troubleshooting
Check No.04
Refer to P.144
Check No.06
Refer to P.146
Check No.11
Refer to P.156
120
system is shut down.
the compressor stops. (The error is cleared when the temperature has dropped below
225°F(107°C).
compressor running time (total time).
(heat exchanger or outdoor temperature thermistor defective)
Be sure to turn off the power switch before connecting or disconnecting
Caution
the connector, or parts damage may occur.
Check No. 06
Check the thermistors.
Functioning
Check No. 04
Check the electronic
expansion valve.
Functioning
Check No. 11
Check the refrigerant line.
Functioning
Malfunctioning
Discharge pipe thermistor
Outdoor unit heat exchanger thermistor
Outdoor temperature thermistor
Malfunctioning
Malfunctioning
Refrigerant shortage
Four-way valve malfunctioning
Water mixed
Stop valve defective
Troubleshooting
Replace the defective
thermistor.
Replace the valve itself or
the coil.
Refer to the refrigerant line
check procedure.
Replace the outdoor unit
PCB.
(R7141)
Service Diagnosis