SiUS04-904
4.3
Freeze-up Protection Control or High Pressure Control
A5
Remote
Controller
Display
High pressure control
Method of
Malfunction
Detection
Freeze-up protection control (operation halt) is activated during cooling operation according to
High pressure control
Malfunction
Decision
Conditions
Freeze-up protection
Operation halt due to clogged air filter of the indoor unit.
Supposed
Operation halt due to dust accumulation on the indoor unit heat exchanger.
Causes
Operation halt due to short-circuit.
Detection error due to faulty indoor unit heat exchanger thermistor.
Detection error due to faulty indoor unit PCB.
100
During heating operations, the temperature detected by the indoor heat exchanger thermistor is
used for the high pressure control (stop, outdoor fan stop, etc.)
the temperature detected by the indoor unit heat exchanger thermistor.
During heating operations, the temperature detected by the indoor heat exchanger thermistor is
above 149°F
(65°C)
When the indoor unit heat exchanger temperature is below 32°F
Troubleshooting
(0°C)
during cooling operation.
Service Diagnosis