Troubleshooting
4.13 High Pressure Control in Cooling
F6
Remote
Controller
Display
High-pressure control (stop, frequency drop, etc.) is activated in the cooling mode if the
Method of
temperature being sensed by the heat exchanger thermistor exceeds the limit.
Malfunction
Detection
Malfunction
Activated when the temperature being sensed by the heat exchanger thermistor rises above
(The error is cleared when the temperature drops below
Decision
Conditions
15/18/24 class
The installation space is not large enough.
Supposed
Faulty outdoor unit fan
Causes
Faulty electronic expansion valve
Faulty defrost thermistor
Faulty outdoor unit PCB
Faulty stop valve
Dirty heat exchanger
Service Diagnosis
09/12 class
149
140
°F.)
129
122
SiUS04-904
°F.
121