Troubleshooting
4.10.2 15/18/24 Class
E8
Remote
Controller
Display
An input overcurrent is detected by checking the input current value being detected by CT with the
Method of
compressor running.
Malfunction
Detection
The following CT input with the compressor running continues for 2.5 seconds.
Malfunction
Decision
The system is shut down if the error occurs 16 times.
Conditions
Clearing condition : Continuous run for about 5 minutes (normal)
Overcurrent due to compressor failure
Supposed
Overcurrent due to defective power transistor
Causes
Overcurrent due to defective inverter main circuit electrolytic capacitor
Overcurrent due to defective outdoor unit PCB
Error detection due to outdoor unit PCB
Overcurrent due to short-circuit
Service Diagnosis
CT input : Above 20 A