Control Specification (09/12 Class)
3.3.4 3-minute Standby
Prohibits turning ON the compressor for 3 minutes after turning it off
(except when defrosting).
3.3.5 Compressor Protection Function
When turning the compressor from OFF to ON, the upper limit of frequency must be set as follows.
The function must not be used when defrosting
3.4

Discharge Pipe Temperature Control

Outline
The discharge pipe temperature is used as the compressor's internal temperature. If the discharge
pipe temperature rises above a certain level, the operating frequency upper limit is set to keep this
temperature from going up further.
Detail
Divide the Zone
Management within the Zones
3.5

Input Current Control

Outline
Detects an input current by the CT while the compressor is running, and sets the frequency upper
limit from such input current.
In case of heat pump model, this control is the upper limit control function of the frequency which
takes priority of the lower limit of four-way valve activating compensation.
40
FCG 1
55
FCG 2
70
FCG 3
85
TCG1
120
TCG2
200
TCG3
470
Zone
Stop zone
When the temperature reaches the stop zone, stop the compressor and
correct abnormality.
Dropping zone
Start the timer, and the frequency is dropping.
Keep zone
Keep the upper limit of frequency.
Return / Reset zone
Cancel the upper limit of frequency.
(Hz)
Dropping zone
Control contents
SiUS04-904
Time (Sec)
(R10540)
Function and Control