SiUS04-904
4.19 Radiation Fin Temperature Rise
L4
Remote
Controller
Display
A radiation fin temperature rise is detected by checking the radiation fin thermistor with the
Method of
compressor on.
Malfunction
Detection
Malfunction
If the radiation fin temperature with the compressor on is above 194°F (90°C).
If a radiation fin temperature rise takes place 4 times successively, the system is shut down.
Decision
The error counter is reset if this or any other error does not occur during the following 60-minute
Conditions
Fin temperature rise due to defective outdoor unit fan
Supposed
Fin temperature rise due to short-circuit
Causes
Fin thermistor defective
Connector in poor contact
Outdoor unit PCB defective
132
compressor running time (total time).
Troubleshooting
Service Diagnosis